2022-05-25 13:54:23GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GENERATOR DISTANCE FROM HOUSE
 OPENINGS - FBC R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) PLEASE PROVIDE FOUNDATION DETAILS.
  
 3) GENERATOR IS SUBJECT TO WIND LOADS - PLEASE PROVIDE
 GENERATOR ATTACHMENT DETAILS TO THE FOUNDATION FROM A
 DESIGN PROFESSIONAL FBC 1609
  