2022-02-02 11:01:251ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011113
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION STATES HVAC AS PER PLANS. THE DESIGN
 CALCULATIONS ARE LABELED #1. THE MECHANICAL DRAWING
 SHOWS 2 SEPARATE SYSTEMS. PLEASE PROVIDE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS FOR THE 2ND MECHANICAL
 SYSTEM.
  
 2) THE DRAWING SUBMITTED SHOWS WALLS BUT DOES NOT SHOW
 DOORS. PLEASE SHOW HOW THE RETURN AIR WILL MOVE FROM
 ONE ROOM TO THE OTHER AND THEN BACK TO THE AHU.
 EXAMPLE: HOW DOES THE RETURN AIR FLOW FROM LIVING ROOM
 BACK TO THE AHU-1 IN THE KITCHEN?
  
 3) DALE V WILL NEED TO PRINT AND SIGN THEIR NAME ON THE
 DRAWING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  