Plan Review Notes For Permit 22011113 |
Permit Number |
22011113 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-02 11:01:25 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22011113 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE APPLICATION STATES HVAC AS PER PLANS. THE DESIGN | | CALCULATIONS ARE LABELED #1. THE MECHANICAL DRAWING | | SHOWS 2 SEPARATE SYSTEMS. PLEASE PROVIDE THE MECHANICAL | | EQUIPMENT SIZING CALCULATIONS FOR THE 2ND MECHANICAL | | SYSTEM. | | | | 2) THE DRAWING SUBMITTED SHOWS WALLS BUT DOES NOT SHOW | | DOORS. PLEASE SHOW HOW THE RETURN AIR WILL MOVE FROM | | ONE ROOM TO THE OTHER AND THEN BACK TO THE AHU. | | EXAMPLE: HOW DOES THE RETURN AIR FLOW FROM LIVING ROOM | | BACK TO THE AHU-1 IN THE KITCHEN? | | | | 3) DALE V WILL NEED TO PRINT AND SIGN THEIR NAME ON THE | | DRAWING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|