Date |
Text |
2022-03-16 07:44:40 | PLEASE ADDRESS THE ENERGY CALCULATIONS, AND MECHANICAL |
| EQUIPMENT SIZING CALCULATIONS FOR BOTH STRUCTURES |
| MENTIONED IN 1ST CYCLE PLAN REVIEW COMMENTS BELOW. ALSO |
| SHOW HOW THE DUCT SYSTEMS WILL BE RAN OUTSIDE OF THE |
| FLOOR CEILING ASSEMBLY. THERE SHALL NOT BE A SCREEN AT |
| THE TERMINATION OF THE DRYER VENT. FBC RES M1502.3 |
| |
| |
| 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22011100 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| A SEPARATE PERMIT WILL BE REQUIRED FOR THE CONVERTING |
| OF THE GARAGE INTO A DUPLEX. |
| PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH |
| BUILDINGS. FBC EC 101.5.1.1.2 |
| PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR BOTH BUILDINGS. FBC EC R403.7 |
| ARE THERE GOING TO BE HOODS ABOVE THE RANGES IN THESE |
| UNITS? IF SO ARE THEY DUCTED TO THE EXTERIOR? IF SO, |
| PLEASE SHOW THE DUCT AND THE TERMINATION LOCATION ON |
| THE DRAWINGS FOR BOTH BUILDINGS. FBC RES M1503.4 |
| PLEASE SHOW THE DRYER EXHAUST DUCTWORK AND TERMINATION |
| LOCATION FOR BOTH BUILDINGS ON THE DRAWINGS. FBC RES |
| M1502 |
| |
| MAIN HOUSE: |
| A COMPLETE REVIEW FOR THIS MAIN BUILDING CANNOT BE |
| COMPLETED AT THIS TIME. |
| |
| 1) SHEET M-1: PLEASE PROVIDE A DETAIL DRAWING OF THE |
| DUCTWORK AND THE BATH EXHAUST FANS PROTECTION WHEN |
| PENETRATING THE RATED FLOOR CEILING ASSEMBLY. FBC 607 |
| |
| CONVERTED GARAGE: |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |