2022-01-31 09:08:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011100
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 A SEPARATE PERMIT WILL BE REQUIRED FOR THE CONVERTING
 OF THE GARAGE INTO A DUPLEX.
 PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH
 BUILDINGS. FBC EC 101.5.1.1.2
 PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR BOTH BUILDINGS. FBC EC R403.7
 ARE THERE GOING TO BE HOODS ABOVE THE RANGES IN THESE
 UNITS? IF SO ARE THEY DUCTED TO THE EXTERIOR? IF SO,
 PLEASE SHOW THE DUCT AND THE TERMINATION LOCATION ON
 THE DRAWINGS FOR BOTH BUILDINGS. FBC RES M1503.4
 PLEASE SHOW THE DRYER EXHAUST DUCTWORK AND TERMINATION
 LOCATION FOR BOTH BUILDINGS ON THE DRAWINGS. FBC RES
 M1502
  
 MAIN HOUSE:
 A COMPLETE REVIEW FOR THIS MAIN BUILDING CANNOT BE
 COMPLETED AT THIS TIME.
  
 1) SHEET M-1: PLEASE PROVIDE A DETAIL DRAWING OF THE
 DUCTWORK AND THE BATH EXHAUST FANS PROTECTION WHEN
 PENETRATING THE RATED FLOOR CEILING ASSEMBLY. FBC 607
  
 CONVERTED GARAGE:
  
 1) PLEASE SHOW THE LOCATION OF THE DRYER EXHAUST IN THE
 WALL, PLEASE BE ADVISED IT CANNOT BE INSIDE THE 2 HOUR
 RATED TENANT SEPARATION WALL UNLESS IT WOULD BE
 PROTECTED INSIDE OF A SHAFT. FBC 604
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  