Plan Review Notes For Permit 22011100 |
Permit Number |
22011100 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-08 08:14:49 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1.) FBC B 107.2.1, PROVIDE INFILL DETAILS FOR | | WINDOWS/DOORS AND FLOORS INCLUDING THE OPENING LEFT | | FROM STAIR REMOVAL BETWEEN 1ST AND 2ND FLOOR. | | 2.) FBC R 302.3, PROVIDE FIRE RATING DETAILS FOR TENANT | | SEPARATION AT WALLS AND FLOORS. | | 3.) FBC B 107.2.1, PROVIDE CORRECTION OF ELEVATION | | VIEWS AT SHEET A-2, AS NORTH AND SOUTH ELEVATIONS | | APPEAR TO BE REVERSED. | | 4.) FBC B 107.2.1, PROVIDE CORRECTION TO PLAN SHEETS | | A-1 & A-2 FOR LOCATION OF STAIRS AS PLAN SHEET A-1 | | INDICATES AN INTERIOR STAIR AND SHEET A-2 INDICATES AN | | EXTERIOR STAIR. | | 5.) FBC EB 1001.2.2, ACCORDING TO CITY RECORDS AND | | SUBMITTED PLANS, THIS APPLICATION INVOLVES A STRUCTURE | | THAT WAS ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE. | | IT'S PROPOSED TO BE CONVERTED TO AN APARTMENT WITH A | | KITCHEN, BEDROOM AND BATHROOM. PLEASE INDICATE AND THAT | | THIS APPLICATION WILL COMPLY WITH THE 2020 FBC EXISTING | | BUILDING CODE, AS THIS IS CONSIDERED A CHANGE OF | | OCCUPANCY. | | | | | | | | |
|