 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, PROVIDE INFILL DETAILS FOR
 WINDOWS/DOORS AND FLOORS INCLUDING THE OPENING LEFT
 FROM STAIR REMOVAL BETWEEN 1ST AND 2ND FLOOR.
 2.) FBC R 302.3, PROVIDE FIRE RATING DETAILS FOR TENANT
 SEPARATION AT WALLS AND FLOORS.
 3.) FBC B 107.2.1, PROVIDE CORRECTION OF ELEVATION
 VIEWS AT SHEET A-2, AS NORTH AND SOUTH ELEVATIONS
 APPEAR TO BE REVERSED.
 4.) FBC B 107.2.1, PROVIDE CORRECTION TO PLAN SHEETS
 A-1 & A-2 FOR LOCATION OF STAIRS AS PLAN SHEET A-1
 INDICATES AN INTERIOR STAIR AND SHEET A-2 INDICATES AN
 EXTERIOR STAIR.
 5.) FBC EB 1001.2.2, ACCORDING TO CITY RECORDS AND
 SUBMITTED PLANS, THIS APPLICATION INVOLVES A STRUCTURE
 THAT WAS ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE.
 IT'S PROPOSED TO BE CONVERTED TO AN APARTMENT WITH A
 KITCHEN, BEDROOM AND BATHROOM. PLEASE INDICATE AND THAT
 THIS APPLICATION WILL COMPLY WITH THE 2020 FBC EXISTING
 BUILDING CODE, AS THIS IS CONSIDERED A CHANGE OF
 OCCUPANCY.
  
  
  
  