2022-07-08 17:16:21 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22011077. |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT |
| THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| BEFORE PERMIT ISSUANCE. |
| |
| ORIGINAL COMMENT: |
| 1-LOT DRAINAGE. |
| PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS |
| AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| 2- OK. |
| |
| 3-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| ORIGINAL COMMENT: |
| A)METAL SHINGLES. PROVIDE COMPLETE AND CURRENT APPROVED |
| PRODUCT APPROVAL. NEED COMPLETE FLORIDA PRODUCT |
| APPROVAL, INCLUDING FLORIDA PRODUCT APPROVAL COVER PAGE |
| SHOWING THE CURRENT CODE OR MIAMI DADE NOA. |
| IF NONE OF THESE OPTIONS IS AVAILABLE, THEN |
| MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL BY |
| SUBMITTING COMPLETE ENGINEERING SIGNED AND SEALED |
| DRAWINGS FOR BUILDING OFFICIAL APPROVAL. FAC |
| 61G20-3.001. |
| |
| RESPONSE: |
| (1)TWO DIFFERENT PRODUCT APPROVALS WERE SUBMITTED. |
| SUBMIT EITHER A COMPLETE MIAMI DADE NOA OR A COMPLETE |
| FLORIDA PRODUCT APPROVAL INCLUDING THE COVER PAGE THAT |
| CORRESPONDS TO THE INFORMATION SUBMITTED. |
| |
| (2) CLEARLY MARK ON PRODUCT APPROVAL WHICH METAL |
| ROOFING FASTENING OPTION IS GOING TO BE USED. NEED THIS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES FOR ALL |
| ROOF ZONES. |
| |
| ORIGINAL COMMENT: |
| B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| |
| RESPONSE: |
| REPEAT COMMENT. SIZE OF MULLION WAS NOT IDENTIFIED ON |
| THE PRODUCT APPROVAL. |
| |
| ORIGINAL COMMENT: |
| C)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| REPEAT COMMENT. PRODUCT APPROVAL FOR INSWING DOOR AS |
| SHOWN ON PLANS WAS NOT SUBMITTED. |
| |
| D)OK. |
| |
| ORIGINAL COMMENT: |
| E)STORAGE EXTERIOR DOOR AS SHOWN ON PLANS. OK. BUT NEED |
| FLORIDA PRODUCT APPROVAL COVER PAGE. |
| |
| RESPONSE: |
| PARTIALLY DONE. DRAWINGS SUBMITTED BUT FLORIDA PRODUCT |
| APPROVAL COVER PAGE WAS NOT SUBMITTED. |
| NOTE: THE FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE |
| IT SHOWS IF PRODUCT IS APPROVED AND CURRENT CODE IN |
| EFFECT. |
| |
| F)OK. |
| |
| ORIGINAL COMMENT: |
| G)UNDERLAYMENT SPECIFIED ON PLANS FOR METAL SHINGLES. |
| |
| RESPONSE: |
| PARTIALLY DONE. INFORMATION SUBMITTED IS MISSING |
| FLORIDA PRODUCT APPROVAL COVER PAGE. |
| NOTE: THE FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE |
| IT SHOWS IF PRODUCT IS APPROVED AND CURRENT CODE IN |
| EFFECT. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 5- WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF |
| RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH |
| SEC. R704 FBC-RESIDENTIAL. |
| NOTE: PLANS SPECIFY T & G WOOD CEILING ALT. W.L. & |
| STUCCO. PROVIDE COMPLETE DETAIL/SPECS FOR ALT. W.L. & |
| STUCCO SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH WIND |
| RESISTANCE. |
| |
| RESPONSE; |
| ENGINEER OF RECORD NEEDS TO SPECIFY FASTENING |
| SPECIFICATIONS. CITING TABLE FROM THE CODE IS NOT |
| ALLOWED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 6- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20 |
| INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 |
| FBC-RESIDENTIAL. |
| NOTE: ENGINEER TO REVIEW AND APPROVE THE REPORT IN |
| WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT SUBMITTED. |
| |
| 7- OK. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |