2022-02-14 13:23:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011077
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS GIVEN ON THE PERMIT, 803 KANUGA DR DOES
 NOT MATCH THE ADDRESS GIVEN ON THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS. PLEASE CORRECT THIS. FBC 107.2.1
  
 2) PLEASE ADD THE DUCT SIZES ON ALL OF THE DUCTWORK.
 FBC 107.2.1
  
 3) THERE APPEARS TO BE A 6X6 GRILL IN THE BATH AT THE
 PATIO AREA, PLEASE SHOW THE SUPPLY DUCT FOR THIS. FBC
 107.2.1
  
 4) PLEASE PROVIDE SPECIFICATIONS FOR THE HOOD FAN
 MOTOR. FBC RES M1503.4
  
 5) THE DRAWING MUST BE SIGNED BY THE DESIGNER.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  