2022-03-23 15:42:18RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011077.
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1-LOT DRAINAGE
 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2-ENERGY CALCULATIONS SUBMITTED:
 NOTE: THIS HOUSE IS A CONTRIBUTING HISTORIC HOUSE.
 ENERGY CALCULATIONS ARE NOT REQUIRED. BUT IF APPLICANT
 WANTS THEM TO BE PART OF THE CONSTRUCTION DOCUMENTS,
 THEN REVISE THEM AS FOLLOWS:
  
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)A/C AREA SPECIFIED ON PAGE 1 DOESN'T MATCH AREA
 SPECIFIED ON PLANS. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C) DOORS INFORMATION SPECIFIED ON PAGE 3 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 NOTE: DOORS TO BE CONSIDERED ARE THE ONES SEPARATING
 A/C AREA FROM NON A/C AREAS.
  
 D) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 3-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)METAL SHINGLES. PROVIDE COMPLETE AND CURRENT APPROVED
 PRODUCT APPROVAL. NEED COMPLETE FLORIDA PRODUCT
 APPROVAL, INCLUDING FLORIDA PRODUCT APPROVAL COVER PAGE
 SHOWING THE CURRENT CODE OR MIAMI DADE NOA.
 IF NONE OF THESE OPTIONS IS AVAILABLE, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL BY
 SUBMITTING COMPLETE ENGINEERING SIGNED AND SEALED
 DRAWINGS FOR BUILDING OFFICIAL APPROVAL. FAC
 61G20-3.001.
  
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 C)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 D)GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 E) STORAGE EXTERIOR DOOR AS SHOWN ON PLANS.
  
 F)CABANA BATH DOOR AS SHOWN ON PLANS.
  
 G) UNDERLAYMENT SPECIFIED ON PLANS FOR METAL SHINGLES.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: PLANS SPECIFY T & G WOOD CEILING ALT. W.L. &
 STUCCO. PROVIDE COMPLETE DETAIL/SPECS FOR ALT. W.L. &
 STUCCO SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH WIND
 RESISTANCE.
  
 6- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ENGINEER TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION IN NEW
 ADDITION. ALSO, SPECIFY SIZE FOR NEW ATTIC ACCESS SHOWN
 IN GARAGE AREA. SEC. R807 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER