Plan Review Notes For Permit 22011061 |
Permit Number |
22011061 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-28 14:23:14 | ELECTRIC REVIEW FAILED | | 1) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION FOR THE | | ENTIRE SERVICE (BOTH UNITS) NEC 215.5 | | 2) PLEASE ADD A NOTE STATING AFCI PROTECTION TO INCLUDE | | NEC 406.4 REQUIREMENTS | | 3) INCLUDE A NOTE CORRECTLY STATING COMPLIANCE WITH | | 210.8 GFCI PROTECTION | | 4) PLEASE DETAIL COMPLETE SCOPE OF ELECTRIC WORK. | | DETAIL ELECTRIC WORK TO BE REMOVED, REPLACED OR | | MODIFIED FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|