2022-02-16 10:39:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010997
 ADD: 1500 N DIXIE HWY
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-582-7880
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 16TH/ 2022
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET:
 1A) UNDER THE HEADING OF BUILDING CODE ANALYSIS THE
 OCCUPANT LOAD IS TAKEN USING A OCCUPANT LOAD FACTOR OF
 100. IN THE 2020 FBC-BUILDING CODE TABLE 1004.5 THE
 OCCUPANT LOAD FACTOR IS TAKEN AT 150 SQ. FT. PLEASE
 UPDATE THE PLANS.
  
 1B) THE LIFE SAFETY PLAN STATES THIS BUILDING IS IN A
 FIRE DISTRICT. PLEASE NOTE THERE HAS NOT BEEN ANY FIRE
 DISTRICTS SINCE THE 2001 FBC BUILDING CODE.
  
 2) SHEET A-2 THE EXISTING DOOR LEADING INTO THE1 HOUR
 FIRE RATED VERTICAL EXIT IS NOT INCLUDED IN THE DOOR
 SCHEDULE, NO FIRE RATING GIVEN PER (FBC-BUILDING TABLE
 716.5) NOR HARDWARE FOR THE EXIT. PLEASE READ, IN THE
 2020 FBC-BUILDING CODE SECTION 1010.1.9.11 EXCEPTION 4,
 NOTE ON PLANS.
  
 3A) SHEET ID-3 ELEVATIONS OF THE RESTROOM SHOW
 COMPLIANCE WITH 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 3B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved