2022-02-10 15:24:35 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-22010969 |
| 2/10/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A SITE PLAN SHOWING THE LOCATIONS OF THE |
| INTERCEPTOR, SAMPLING PORT, CLEANOUTS, VENTS, AND THE |
| GREASE WASTE PIPING RUN FROM THE BUILDING- SECTION |
| 107.2.1 WPB. INDICATE ON THE PLAN THE NAME OF THE |
| BUSINESS THE INTERCEPTOR IS SERVING. |
| |
| 2) PROVIDE SIZING CALCULATIONS- SECTION 1003.3.5 FBC P. |
| PLEASE NOTE THAT THE SEAT SIZING FORMULA IN FAC RULE |
| 64E6 IS NO LONGER USED FOR SIZING INTERCEPTORS |
| CONNECTED TO THE CITY OF WPB SEWER SYSTEM. |
| HYDROMECHANICAL INTERCEPTORS SHALL BE FOR THE EXPECTED |
| MAXIMUM FLOW RATE IN GALLONS PER MINUTE THROUGH THE |
| DEVICE. THE CALCULATIONS SHALL BE IN ACCORDANCE WITH |
| ASME A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA |
| B481.3 OR PDI G101, AND SHALL INCLUDE DRAINAGE FROM ALL |
| FIXTURES DISCHARGING FATS, OILS, OR GREASE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |