Plan Review Notes
Plan Review Notes For Permit 22010966
Permit Number 22010966
Review Stop B
Sequence Number 4
Notes
Date Text
2022-06-28 17:55:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010966
 ADD: 185 BANYAN BLVD.
 CONT: MGM GENERAL CONTRACTING
 TEL: 954-532-9620
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: TUES. JULY 28TH/ 2022
 ACTION: DENIED
  
 1) BUILDING PROVISO: SHEET A5.1DETAIL # 6 CANOPY
 COLUMNS FIELD WIELDING AND SHEET S3 & S-4 DETAILS 1 &
 2. WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE ACTING CHIEF BUILDING INSPECTOR RICHARD BRUNELLE
 AT 561-805-6670.
  
 2) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 RETRACTABLE AWNINGS, UNDER SEPARATE PERMIT.
 FABRIC AWNINGS, UNDER SEPARATE PERMIT.
  
 3) PLEASE UNDERSTAND YOUR ROOFING PRODUCT APPROVAL, NOA
 18-0108.20 VERSION 3 SUBMITTED ON 6/09/2022. IN THE NOA
 PAGE 14 OF 20 HIGHLIGHTED, ZONE ONE GOOD FOR -60 PSF,
 DOES NOT MEET THE NEGATIVE PRESSURESS IN ROOF ZONE 1 OF
 -92.86PSF, LIMITATION # 7 READ THE LIMITATION. REVIEW
 SHEET S-4 THAT GIVES YOU THE ROOF PRESSURES IN VASD
 JUST LIKE THE PRODUCT APPROVAL.
  
 ROOF ZONE 1 -92.86 @ 10 S. F.
 ROOF ZONE 2 -117,29 @ 10 S. F.
 ROOF ZONE 3 -139.12 @ 10 S. F.
  
 YOUR ROOF ZONE 1 HAS TO MEET AT A MINIMUM -92.86 PSF
 AND THE ROOFING PRODUCT APPROVAL FOR THE SYSTEM HAS TO
 HAVE A LIMITATION # 7 FOR ENHANCED FASTENING IN ROOF
 ZONES 2 & 3. THE ENHANCED ROOF ZONE FASTENING SCHEDULE
 HAS TO BE COMPLETED BY A ENGINEER, PREFERABLY THE
 STRUCTURAL ENGINEER, OTHERWISE A DELEGATE ENGINEER HAS
 TO HAVE THEIR WORK REVIEWED BY THE STRUCTURAL ENGINEER.
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  