Date |
Text |
2022-05-17 11:19:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22010966 |
| ADD: 185 BANYAN BLVD. |
| CONT: MGM GENERAL CONTRACTING |
| TEL: 954-532-9620 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| NO TRANSMITTAL LETTER WAS SUBMITTED FOR BUILDING |
| REVIEW. A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| 3RD REVIEW |
| DATE: TUES. MAY 17TH/ 2022 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. |
| 3) SHEET A2.02: |
| |
| 3) COMPLIED. SHEET A2.02 NOTE 10 NEW SERVICE STATION |
| MAX. HEIGHT OF STATION TO BE 34 INCHES |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED, RESTROOM DOORS OUTSWING. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) SHEET 6-3 VERSES A0.01 PROJECT DATA: |
| |
| 8A) SHEET A5.01 3D REQUEST THERE ARE NOTES ON THE PLANS |
| FOR THE STEEL COLUMNS CLAD WITH WHITE WASHED WOOD |
| STATING INHERENTLY THIS WOOD HAS A ONE HOUR FIRE |
| RATING. THERE IS NO INFORMATION AS TO HOW THE COLUMNS |
| ARE GOING TO BE ONE-HOUR FIRE RESISTANCE RATING FOR THE |
| PRIMARY STRUCTURAL FRAME PER 2020 FBC-BUILDING CODE |
| TABLE 601 & SECTION 602.3. SUBMITTED THIS REVIEW SALES |
| BROCHURE FOR FLAME OFF WITHIN THIS DOCUMENT IT STATES |
| SEE ICC REPORT ESR-3874 AND UL D38327 NEITHER OF THESE |
| DOCUMENTS WERE SUBMITTED WHERE THIS PRODUCT CAN BE |
| USED. |
| 2ND REQUEST. THE RESPONSE LETTER FOR BUILDING TYPE IIIA |
| CONSTRUCTION IS UL V340 ASSEMBLY. PLEASE PROVIDE THE UL |
| V 340 ASSEMBLY SINCE THE INSPECTOR IN THE FIELD WILL |
| NOT HAVE A UL ASSEMBLY BOOK. DETAIL 2 INDICATES 6X20 |
| GA. METAL STUDS, 5/8-INCH CDX PLYWOOD FOR WALLS, AND |
| ROOF CDX PLYWOOD FOR THE DECK. PLEASE REVIEW THE |
| REQUIREMENTS FOR EXTERIOR BEARING WALLS REQUIRING A |
| 2-HOUR FIR RATING (TABLE 601) AND ROOF CONSTRUCTION |
| (TABLE 601) 1 HOUR INCLUDING SECONDARY FRAMING MEMBERS. |
| SECTION 602.3 FIRE RETARDANT TREATED WOOD. |
| 1ST ROUND COMMENT. SHEET A0.01 PROJECT DATA LIST THE |
| BUILDING TYPE AS A TYPE IIIA. DETAIL 2 INDICATES 6X20 |
| GA. METAL STUDS, 5/8-INCH CDX PLYWOOD FOR WALLS, AND |
| ROOF CDX PLYWOOD FOR THE DECK. PLEASE REVIEW THE |
| REQUIREMENTS FOR EXTERIOR BEARING WALLS REQUIRING A |
| 2-HOUR FIR RATING (TABLE 601) AND ROOF CONSTRUCTION |
| (TABLE 601) 1 HOUR INCLUDING SECONDARY FRAMING MEMBERS. |
| SECTION 602.3 FIRE RETARDANT TREATED WOOD. |
| |
| 8B)(1) 3RD REQUEST. SHEET A5.01 THE ROOF CEILING |
| ASSEMBLY HAS A STEEL FRAMING HORIZONTAL FRAMING |
| MEMBERS. THERE IS NO INFORMATION AS TO HOW THE ONE-HOUR |
| FIRE RESISTANCE RATING FOR THE PRIMARY STRUCTURAL FRAME |
| PER 2020 FBC-BUILDING CODE TABLE 601 & SECTION 602.3 |
| WILL OCCUR. THERE ARE 2 NOTES ONE FOR 2 HR. FIRE RATING |
| FOR HORIZONTAL ASSEMBLIES, 2 ? SHEETS FIRE RETARDANT |
| TREATED PLYWOOD, PAPER BACK LATH, AND ? INCH OF STUCCO |
| PLEASE PROVIDE THE UL ASSEMBLY. |
| THE SECOND NOTE AGAIN STATES YOU CAN GET A 1 HOUR FIRE |
| RATING FROM MANUFACTURED WHITE WASHED WOOD, PLEASE |
| PROVIDE THE TESTING REPORT FOR USE IN THE HORIZONTAL |
| PLANE. |
| 2ND REQUEST. THE RESPONSE INDICATES INHERENTLY FIRE |
| RATED WHITEWASHED TEAK WOOD. PLEASE PROVIDE TESTING |
| REPORT AND OR UL REPORT WHERE TEAK MEETS A 1-HOUR FIRE |
| RATING. |
| ROOF OVER BAR FRAMING PLAN. THIS DETAIL INDICATES STEEL |
| COLUMNS AND ROOF FRAMING LAYOUT. THERE IS NO |
| INFORMATION AS TO HOW THE COLUMNS ARE GOING TO BE |
| ONE-HOUR FIRE RESISTANCE RATING FOR THE PRIMARY |
| STRUCTURAL FRAME PER 2020 FBC-BUILDING CODE TABLE 601 & |
| SECTION 602.3. |
| |
| 8B)(2) 2ND REQUEST. THE RESPONSE NOTES ON THE PLAN |
| STATES 2HOUR FIRE RATING UL V340 ASSEMBLY. PLEASE |
| PROVIDE WHERE THE UL V340 WALL ASSEBMBLY HAS EVER BEEN |
| TESTED FOR HORIZONTALLY. |
| ROOF OVER BAR FRAMING PLAN. THIS DETAIL INDICATES |
| PRIMARY AND SECONDARY ROOF FRAMING MEMBERS AS WELL AS |
| NOTE 1 ROOF DECK SHALL BE B DECK W/ 5/8-INCH DIA. |
| PUDDLE WELD. THE PLAN IS SILENT AS TO COMPLIANCE WITH |
| 1-HOUR FIRE RESISTANCE RATING REQUIREMENTS IN TABLE |
| 601. |
| |
| 8C) COMPLIED, 2020 FBC-B TABLE 721.1.3(9 |
| |
| 8D) BUILDING PROVISO: DETAIL # 6 CANOPY COLUMNS FIELD |
| WIELDING AND SHEET S-4 DETAILS 1 & 2. WELDED OR BOLTED |
| CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| CERTIFICATION WILL BE REQUIRED. |
| THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| INSPECTION. |
| 2020 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR |
| RICHARD BRUNELLE AT 561-805-6670. |
| |
| 9) COMPLIED. SHEET S-1 WINDOW/ DOOR WALL PRESSURES. |
| SHEET S-4 ROOF PRESSURES. |
| |
| 10) SEMI-COMPLIED. COMPONENTS & CLADDING. 3RD REQUEST, |
| PRODUCT APPROVAL. PLEASE SUBMIT THE COMPONENTS AND |
| CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31(C) WALL LOUVER PRODUCT APPROVAL. |
| W. P. B. 107.3.4. PRODUCT APPROVALS. |
| NOA 22-0105.05 350 ALUMINUM FIXED WINDOW |
| NOA 21-0708.15 DOUBLE STEEL DOOR SERIES LS1875 |
| WALL LOUVER |
| NOA 18-0108.20 CARLISLE SURE WELD SINGLE PLY TPO |
| |
| THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 12) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS: |
| RETRACTABLE AWNINGS, UNDER SEPARATE PERMIT. |
| FABRIC AWNINGS, UNDER SEPARATE PERMIT. |
| |
| 13) COMPLIED. NOA 22-0105.05 ECO WINDOWS 350 ALUMINUM |
| FIXED WINDOWS L. M. I. |
| |
| 14) 3RD REQUEST. NOA 18-0108.20 ROOFING: SHEET A2.06 |
| LIST COMPONENTS TO MAKE UP A ROOFING COMPONENT AND |
| CLADDING, BUT IN THE ROOFING PRODUCT APPROVAL THE |
| CONTRACTOR NOR DESIGNER OF RECORD HAS NOT IDENTIFIED ON |
| PAGES 5-20 WHICH SUB-SYSTEM IS TO INSTALLED, IDENTIFIED |
| MAXIMUM DESIGN PRESSURE ASSOCIATED WITH THE SUB-SYSTEM |
| AND IF THE SUB-SYSTEM HAS GENERAL LIMITATION 7 WHICH |
| ALLOWS FOR ENHANCED FASTENING IN ZONES 2 & 3 OR |
| LIMITATION 9 WHICH DOES NOT ALLOW FOR ENHANCED |
| FASTENING IN ZONES 2 & 3. PLEASE NOTE IF THE SUB-SYSTEM |
| LIST LIMITATION 7 THEN THE ENHANCED FASTENING HAS TO BE |
| SIGNED AND SEALED BY A QUALIFIED DESIGN PROFESSIONAL. |
| 2ND REQUEST. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 15-17) COMPLIED. |
| |
| 18) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |