Plan Review Notes
Plan Review Notes For Permit 22010966
Permit Number 22010966
Review Stop B
Sequence Number 3
Notes
Date Text
2022-05-17 11:19:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22010966
 ADD: 185 BANYAN BLVD.
 CONT: MGM GENERAL CONTRACTING
 TEL: 954-532-9620
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 NO TRANSMITTAL LETTER WAS SUBMITTED FOR BUILDING
 REVIEW. A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 3RD REVIEW
 DATE: TUES. MAY 17TH/ 2022
 ACTION: DENIED
  
 1-2) COMPLIED.
 3) SHEET A2.02:
  
 3) COMPLIED. SHEET A2.02 NOTE 10 NEW SERVICE STATION
 MAX. HEIGHT OF STATION TO BE 34 INCHES
  
 4) COMPLIED.
  
 5) COMPLIED, RESTROOM DOORS OUTSWING.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) SHEET 6-3 VERSES A0.01 PROJECT DATA:
  
 8A) SHEET A5.01 3D REQUEST THERE ARE NOTES ON THE PLANS
 FOR THE STEEL COLUMNS CLAD WITH WHITE WASHED WOOD
 STATING INHERENTLY THIS WOOD HAS A ONE HOUR FIRE
 RATING. THERE IS NO INFORMATION AS TO HOW THE COLUMNS
 ARE GOING TO BE ONE-HOUR FIRE RESISTANCE RATING FOR THE
 PRIMARY STRUCTURAL FRAME PER 2020 FBC-BUILDING CODE
 TABLE 601 & SECTION 602.3. SUBMITTED THIS REVIEW SALES
 BROCHURE FOR FLAME OFF WITHIN THIS DOCUMENT IT STATES
 SEE ICC REPORT ESR-3874 AND UL D38327 NEITHER OF THESE
 DOCUMENTS WERE SUBMITTED WHERE THIS PRODUCT CAN BE
 USED.
 2ND REQUEST. THE RESPONSE LETTER FOR BUILDING TYPE IIIA
 CONSTRUCTION IS UL V340 ASSEMBLY. PLEASE PROVIDE THE UL
 V 340 ASSEMBLY SINCE THE INSPECTOR IN THE FIELD WILL
 NOT HAVE A UL ASSEMBLY BOOK. DETAIL 2 INDICATES 6X20
 GA. METAL STUDS, 5/8-INCH CDX PLYWOOD FOR WALLS, AND
 ROOF CDX PLYWOOD FOR THE DECK. PLEASE REVIEW THE
 REQUIREMENTS FOR EXTERIOR BEARING WALLS REQUIRING A
 2-HOUR FIR RATING (TABLE 601) AND ROOF CONSTRUCTION
 (TABLE 601) 1 HOUR INCLUDING SECONDARY FRAMING MEMBERS.
 SECTION 602.3 FIRE RETARDANT TREATED WOOD.
 1ST ROUND COMMENT. SHEET A0.01 PROJECT DATA LIST THE
 BUILDING TYPE AS A TYPE IIIA. DETAIL 2 INDICATES 6X20
 GA. METAL STUDS, 5/8-INCH CDX PLYWOOD FOR WALLS, AND
 ROOF CDX PLYWOOD FOR THE DECK. PLEASE REVIEW THE
 REQUIREMENTS FOR EXTERIOR BEARING WALLS REQUIRING A
 2-HOUR FIR RATING (TABLE 601) AND ROOF CONSTRUCTION
 (TABLE 601) 1 HOUR INCLUDING SECONDARY FRAMING MEMBERS.
 SECTION 602.3 FIRE RETARDANT TREATED WOOD.
  
 8B)(1) 3RD REQUEST. SHEET A5.01 THE ROOF CEILING
 ASSEMBLY HAS A STEEL FRAMING HORIZONTAL FRAMING
 MEMBERS. THERE IS NO INFORMATION AS TO HOW THE ONE-HOUR
 FIRE RESISTANCE RATING FOR THE PRIMARY STRUCTURAL FRAME
 PER 2020 FBC-BUILDING CODE TABLE 601 & SECTION 602.3
 WILL OCCUR. THERE ARE 2 NOTES ONE FOR 2 HR. FIRE RATING
 FOR HORIZONTAL ASSEMBLIES, 2 ? SHEETS FIRE RETARDANT
 TREATED PLYWOOD, PAPER BACK LATH, AND ? INCH OF STUCCO
 PLEASE PROVIDE THE UL ASSEMBLY.
 THE SECOND NOTE AGAIN STATES YOU CAN GET A 1 HOUR FIRE
 RATING FROM MANUFACTURED WHITE WASHED WOOD, PLEASE
 PROVIDE THE TESTING REPORT FOR USE IN THE HORIZONTAL
 PLANE.
 2ND REQUEST. THE RESPONSE INDICATES INHERENTLY FIRE
 RATED WHITEWASHED TEAK WOOD. PLEASE PROVIDE TESTING
 REPORT AND OR UL REPORT WHERE TEAK MEETS A 1-HOUR FIRE
 RATING.
 ROOF OVER BAR FRAMING PLAN. THIS DETAIL INDICATES STEEL
 COLUMNS AND ROOF FRAMING LAYOUT. THERE IS NO
 INFORMATION AS TO HOW THE COLUMNS ARE GOING TO BE
 ONE-HOUR FIRE RESISTANCE RATING FOR THE PRIMARY
 STRUCTURAL FRAME PER 2020 FBC-BUILDING CODE TABLE 601 &
 SECTION 602.3.
  
 8B)(2) 2ND REQUEST. THE RESPONSE NOTES ON THE PLAN
 STATES 2HOUR FIRE RATING UL V340 ASSEMBLY. PLEASE
 PROVIDE WHERE THE UL V340 WALL ASSEBMBLY HAS EVER BEEN
 TESTED FOR HORIZONTALLY.
 ROOF OVER BAR FRAMING PLAN. THIS DETAIL INDICATES
 PRIMARY AND SECONDARY ROOF FRAMING MEMBERS AS WELL AS
 NOTE 1 ROOF DECK SHALL BE B DECK W/ 5/8-INCH DIA.
 PUDDLE WELD. THE PLAN IS SILENT AS TO COMPLIANCE WITH
 1-HOUR FIRE RESISTANCE RATING REQUIREMENTS IN TABLE
 601.
  
 8C) COMPLIED, 2020 FBC-B TABLE 721.1.3(9
  
 8D) BUILDING PROVISO: DETAIL # 6 CANOPY COLUMNS FIELD
 WIELDING AND SHEET S-4 DETAILS 1 & 2. WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 9) COMPLIED. SHEET S-1 WINDOW/ DOOR WALL PRESSURES.
 SHEET S-4 ROOF PRESSURES.
  
 10) SEMI-COMPLIED. COMPONENTS & CLADDING. 3RD REQUEST,
 PRODUCT APPROVAL. PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(C) WALL LOUVER PRODUCT APPROVAL.
 W. P. B. 107.3.4. PRODUCT APPROVALS.
 NOA 22-0105.05 350 ALUMINUM FIXED WINDOW
 NOA 21-0708.15 DOUBLE STEEL DOOR SERIES LS1875
 WALL LOUVER
 NOA 18-0108.20 CARLISLE SURE WELD SINGLE PLY TPO
  
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 12) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 RETRACTABLE AWNINGS, UNDER SEPARATE PERMIT.
 FABRIC AWNINGS, UNDER SEPARATE PERMIT.
  
 13) COMPLIED. NOA 22-0105.05 ECO WINDOWS 350 ALUMINUM
 FIXED WINDOWS L. M. I.
  
 14) 3RD REQUEST. NOA 18-0108.20 ROOFING: SHEET A2.06
 LIST COMPONENTS TO MAKE UP A ROOFING COMPONENT AND
 CLADDING, BUT IN THE ROOFING PRODUCT APPROVAL THE
 CONTRACTOR NOR DESIGNER OF RECORD HAS NOT IDENTIFIED ON
 PAGES 5-20 WHICH SUB-SYSTEM IS TO INSTALLED, IDENTIFIED
 MAXIMUM DESIGN PRESSURE ASSOCIATED WITH THE SUB-SYSTEM
 AND IF THE SUB-SYSTEM HAS GENERAL LIMITATION 7 WHICH
 ALLOWS FOR ENHANCED FASTENING IN ZONES 2 & 3 OR
 LIMITATION 9 WHICH DOES NOT ALLOW FOR ENHANCED
 FASTENING IN ZONES 2 & 3. PLEASE NOTE IF THE SUB-SYSTEM
 LIST LIMITATION 7 THEN THE ENHANCED FASTENING HAS TO BE
 SIGNED AND SEALED BY A QUALIFIED DESIGN PROFESSIONAL.
 2ND REQUEST. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 15-17) COMPLIED.
  
 18) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  