Date |
Text |
2022-04-21 15:30:46 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22010966 185 BANYAN BLVD |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| PLEASE NOTE THAT THE ARCHITECT DID NOT RESPOND TO MY |
| COMMENTS CONCERNING ACCESSIBILITY. SOME WERE CORRECTED |
| AS A RESULT OF HIS RESPONSE TO THE BUILDING REVIEW. |
| OTHERS STILL NEED TO BE ADDRESSED OR CLARIFIED. |
| |
| 1.SECOND REQUEST: PLAN SHEET A0.01/ADA COMPLIANCE NOTE: |
| PER WPB FBC 107.2.1, REVISE NOTE TO SHOW COMPLIANCE |
| WITH THE 2020 FLORIDA ACCESSIBILITY CODE. |
| |
| 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| ***A) COMPLIED |
| ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 59 INCHES MINIMUM FOR FLOOR MOUNTED WATER |
| CLOSETS MEASURED PERPENDICULAR FROM THE REAR WALL PER |
| 604.8.1.1. |
| SECOND REQUEST: DETAIL 1 ON A3.01AND A3.02 INDICATE |
| CLEARANCE AROUND A WATER CLOSET BUT DOES NOT PROVIDE |
| DIMENSIONS. PER WPB FBC 107.2.1, PROVIDE DIMENSIONS. |
| ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| WALL PER FBC ACC 604.5.1 |
| NEW COMMENT: A3.03 PROVIDES REQUIRED INFORMATION, |
| HOWEVER, DETAIL 4 AND DETAIL 1 ON A3.01 AND A3.02 IS |
| INCORRECT. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE |
| A3.01 AND A3.02 WITH A3.03. |
| ***D) COMPLIED |
| ***E) COMPLIED |
| ***F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 |
| AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN |
| FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| ACC 604.7. |
| NEW COMMENT: DETAIL ON A3.03 CALLS FOR TOILET PAPER |
| DISPENSER TO COMPLY WITH FAC 604.74.5.1. THIS APPEARS |
| TO BE A MISPRINT AND SHOULD BE FAC 704.1. PER WPB FBC |
| 107.2.1, PLEASE CLARIFY. |
| DETAIL 4 SHOWING TOILET PAPER DISPENSER ON A3.01 AND |
| A3.02 IS INCORRECT. PER WPB FBC 107.2.1, CLARIFY AND |
| RECONCILE A3.01 AND A3.02 WITH CORRECTED A3.03. |
| ***G) COMPLIED |
| ***H) COMPLIED |
| ***I) COMPLIED |
| ***J): COMPLIED |
| ***K) SECOND REQUEST; MIRRORS LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED |
| ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH |
| THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES |
| (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER |
| FBC ACC 603.3. |
| TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS |
| TO THE BOTTOM EDGE OF THE "REFLECTING" SURFACE OF THE |
| MIRROR. |
| |
| 3. SECOND REQUEST: PLAN SHEET A0.03/PLUMBING |
| FIXTURES/TABLE 403.1 FBC PLUMBING: PER WPB FBC 107.2.1, |
| PLEASE CONFIRM THAT THE PLUMBING FIXTURES, WHICH ARE |
| ALREADY IN PLACE, IS NOT PART OF THE ORIGINAL |
| CALCULATIONS FOR THE EXISTING RESTAURANT SPACE. |
| |
| 4. PLAN SHEET P3.01/ WATER HEATER DETAIL: PRV AS PER |
| PLUMBING LEGEND SYMBOLS AND ABBREVIATIONS APPEARS TO |
| INDICATE A PRESSURE REDUCING VALVE; THE SYMBOL ITSELF |
| DOES NOT MATCH. IT IS NOTED THAT THE PRV APPEARS NOT TO |
| CONNECT TO THE WATER HEATER. PER WPB FBC 107.2.1, |
| CLARIFY; IF THIS IS ACTUALLY A PRESSURE RELIEF VALVE |
| THAT DISCHARGES TO THE ATMOSPHERE, PROVIDE A POINT OF |
| TERMINATION. COMPLIED |
| NEW COMMENT: P-301/WATER HEATER DETAIL; DISCHARGE TO |
| ROOF DRAIN SHALL BE THROUGH AN AIR GAP 2X DIAMETER, |
| SHALL NOT DISCHARGE IN A MANNER THAT WOULD CAUSE |
| PERSONAL INJURY OR STRUCTURAL DAMAGE AND SHALL NOT BE |
| TRAPPED. THE TERMINATION POINT SHALL BE READILY |
| OBSERVABLE BY THE BUILDING OCCUPANTS. FBC PL 504.6 (6) |
| (7) (8) (10). ADD NOTE STATING THE SAME. |
| NEW COMMENT: IS PRV AT COLD WATER INLET A PRESSURE |
| RELIEF VALVE. ABBREVIATION INDICATES PRESSURE REDUCING |
| VALVE, BUT THE DETAIL DOES NOT SHOW AN IN-LINE VALVE. |
| PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| |
| 5. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL FOR |
| THE WATER HEATER. |
| MEP RESPONSE IS "PLEASE SEE THE ATTACHED |
| SPECIFICATIONS." I HAVE LOOKED FOR THE SUBMITTAL BUT IT |
| DOES NOT APPEAR TO HAVE BEEN UPLOADED. |
| |
| 6. GREASY WASTE: SEE BELOW. |
| ?A) COMPLIED; THERE IS NO GREASY WASTE |
| ?B) COMPLIED; THERE IS NO GREASY WASTE |
| |
| 7. PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER |
| DIAGRAMS(S), CALCULATIONS FOR NEW STORM DRAINS AND |
| CLARIFICATIONS AS TO HOW THE NEW ROOF DRAINAGE WILL |
| INTEGRATE WITH THE EXISTING STORM WATER SYSTEM(S). |
| INCLUDE ANY OVERFLOW, SECONDARY SYSTEMS THAT MAY BE |
| REQUIRED. CLEARLY SHOW ALL PIPING, GUTTERS, SCUPPERS, |
| DOWNSPOUTS. SHOW COMPLIANCE WITH FBC PL 1106.2 THROUGH |
| 1106.6 INCLUDING ALL TABLES. |
| STILL NEED RASER DIAGRAM FOR NEW SCUPPER,NEW PIPING TO |
| EXISTING STORM DRAIN POC. NEED SCUPPER SIZING. PLEASE |
| SHOW THE EXISTING TRENCH DRAIN NOTED IN THE MEP |
| NARRATIVE. |
| |
| 8. COMPLIED |
| |
| 9. COMPLIED |
| |
| 10. COMPLIED |
| |
| 11. COMPLIED |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING |
| WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| NEW COMMENT: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, |
| PROVIDE NOTE ON P-302 "DEFERRED SUBMITTAL |
| MANUFACTURER'S SPECIFICATION/UL AND INSTALLATION GUIDES |
| FOR EACH PRO-SET FIRE ASSEMBLY TO BE USED SHALL BE |
| PROVIDED. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON |
| SITE PRIOR TO FIRST INSPECTION. PROCEED AT YOUR OWN |
| RISK." |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |