Plan Review Notes
Plan Review Notes For Permit 22010966
Permit Number 22010966
Review Stop P
Sequence Number 2
Notes
Date Text
2022-04-21 15:30:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010966 185 BANYAN BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 PLEASE NOTE THAT THE ARCHITECT DID NOT RESPOND TO MY
 COMMENTS CONCERNING ACCESSIBILITY. SOME WERE CORRECTED
 AS A RESULT OF HIS RESPONSE TO THE BUILDING REVIEW.
 OTHERS STILL NEED TO BE ADDRESSED OR CLARIFIED.
  
 1.SECOND REQUEST: PLAN SHEET A0.01/ADA COMPLIANCE NOTE:
 PER WPB FBC 107.2.1, REVISE NOTE TO SHOW COMPLIANCE
 WITH THE 2020 FLORIDA ACCESSIBILITY CODE.
  
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ***A) COMPLIED
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 59 INCHES MINIMUM FOR FLOOR MOUNTED WATER
 CLOSETS MEASURED PERPENDICULAR FROM THE REAR WALL PER
 604.8.1.1.
 SECOND REQUEST: DETAIL 1 ON A3.01AND A3.02 INDICATE
 CLEARANCE AROUND A WATER CLOSET BUT DOES NOT PROVIDE
 DIMENSIONS. PER WPB FBC 107.2.1, PROVIDE DIMENSIONS.
 ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 NEW COMMENT: A3.03 PROVIDES REQUIRED INFORMATION,
 HOWEVER, DETAIL 4 AND DETAIL 1 ON A3.01 AND A3.02 IS
 INCORRECT. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE
 A3.01 AND A3.02 WITH A3.03.
 ***D) COMPLIED
 ***E) COMPLIED
 ***F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.7.
 NEW COMMENT: DETAIL ON A3.03 CALLS FOR TOILET PAPER
 DISPENSER TO COMPLY WITH FAC 604.74.5.1. THIS APPEARS
 TO BE A MISPRINT AND SHOULD BE FAC 704.1. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
 DETAIL 4 SHOWING TOILET PAPER DISPENSER ON A3.01 AND
 A3.02 IS INCORRECT. PER WPB FBC 107.2.1, CLARIFY AND
 RECONCILE A3.01 AND A3.02 WITH CORRECTED A3.03.
 ***G) COMPLIED
 ***H) COMPLIED
 ***I) COMPLIED
 ***J): COMPLIED
 ***K) SECOND REQUEST; MIRRORS LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER
 FBC ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE BOTTOM EDGE OF THE "REFLECTING" SURFACE OF THE
 MIRROR.
  
 3. SECOND REQUEST: PLAN SHEET A0.03/PLUMBING
 FIXTURES/TABLE 403.1 FBC PLUMBING: PER WPB FBC 107.2.1,
 PLEASE CONFIRM THAT THE PLUMBING FIXTURES, WHICH ARE
 ALREADY IN PLACE, IS NOT PART OF THE ORIGINAL
 CALCULATIONS FOR THE EXISTING RESTAURANT SPACE.
  
 4. PLAN SHEET P3.01/ WATER HEATER DETAIL: PRV AS PER
 PLUMBING LEGEND SYMBOLS AND ABBREVIATIONS APPEARS TO
 INDICATE A PRESSURE REDUCING VALVE; THE SYMBOL ITSELF
 DOES NOT MATCH. IT IS NOTED THAT THE PRV APPEARS NOT TO
 CONNECT TO THE WATER HEATER. PER WPB FBC 107.2.1,
 CLARIFY; IF THIS IS ACTUALLY A PRESSURE RELIEF VALVE
 THAT DISCHARGES TO THE ATMOSPHERE, PROVIDE A POINT OF
 TERMINATION. COMPLIED
 NEW COMMENT: P-301/WATER HEATER DETAIL; DISCHARGE TO
 ROOF DRAIN SHALL BE THROUGH AN AIR GAP 2X DIAMETER,
 SHALL NOT DISCHARGE IN A MANNER THAT WOULD CAUSE
 PERSONAL INJURY OR STRUCTURAL DAMAGE AND SHALL NOT BE
 TRAPPED. THE TERMINATION POINT SHALL BE READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS. FBC PL 504.6 (6)
 (7) (8) (10). ADD NOTE STATING THE SAME.
 NEW COMMENT: IS PRV AT COLD WATER INLET A PRESSURE
 RELIEF VALVE. ABBREVIATION INDICATES PRESSURE REDUCING
 VALVE, BUT THE DETAIL DOES NOT SHOW AN IN-LINE VALVE.
 PER WPB FBC 107.2.1, PLEASE CLARIFY.
  
 5. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL FOR
 THE WATER HEATER.
 MEP RESPONSE IS "PLEASE SEE THE ATTACHED
 SPECIFICATIONS." I HAVE LOOKED FOR THE SUBMITTAL BUT IT
 DOES NOT APPEAR TO HAVE BEEN UPLOADED.
  
 6. GREASY WASTE: SEE BELOW.
 ?A) COMPLIED; THERE IS NO GREASY WASTE
 ?B) COMPLIED; THERE IS NO GREASY WASTE
  
 7. PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAMS(S), CALCULATIONS FOR NEW STORM DRAINS AND
 CLARIFICATIONS AS TO HOW THE NEW ROOF DRAINAGE WILL
 INTEGRATE WITH THE EXISTING STORM WATER SYSTEM(S).
 INCLUDE ANY OVERFLOW, SECONDARY SYSTEMS THAT MAY BE
 REQUIRED. CLEARLY SHOW ALL PIPING, GUTTERS, SCUPPERS,
 DOWNSPOUTS. SHOW COMPLIANCE WITH FBC PL 1106.2 THROUGH
 1106.6 INCLUDING ALL TABLES.
 STILL NEED RASER DIAGRAM FOR NEW SCUPPER,NEW PIPING TO
 EXISTING STORM DRAIN POC. NEED SCUPPER SIZING. PLEASE
 SHOW THE EXISTING TRENCH DRAIN NOTED IN THE MEP
 NARRATIVE.
  
 8. COMPLIED
  
 9. COMPLIED
  
 10. COMPLIED
  
 11. COMPLIED
  
 12. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
 NEW COMMENT: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE NOTE ON P-302 "DEFERRED SUBMITTAL
 MANUFACTURER'S SPECIFICATION/UL AND INSTALLATION GUIDES
 FOR EACH PRO-SET FIRE ASSEMBLY TO BE USED SHALL BE
 PROVIDED. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON
 SITE PRIOR TO FIRST INSPECTION. PROCEED AT YOUR OWN
 RISK."
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS