Plan Review Notes For Permit 22010966 |
Permit Number |
22010966 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-05-05 13:13:53 | CODES IN EFFECT: | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E101 | | | | FOLLOWING CIRCUITS TO BE GFCI PROTECTED PER | | 210.8(B)(2-5) 125 VOLT AND UPTO 150 VOLT TO GROUND | | OUTLETS. | | RT1, 2, 3-5, 4 , 6, 7. 8, 9, 10, 11, 12, 14, 15, 16, | | 17-19, 21, 27, 29-31,33-35, 37-39, 40 | | | | PAGE E201 | | | | NEED A LOAD CALCULATION ON THE 800A MAIN, FAULT CURRENT | | FOR THE NEW PANEL, BREAKERS. 215.5, 110.10 |
|