2022-03-01 13:21:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010966 185 BANYAN BLVD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PLAN SHEET A0.01/ADA COMPLIANCE NOTE: PER WPB FBC
 107.2.1, REVISE NOTE TO SHOW COMPLIANCE WITH THE 2020
 FLORIDA ACCESSIBILITY CODE.
  
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ...A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ...B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 59 INCHES MINIMUM FOR FLOOR MOUNTED WATER
 CLOSETS MEASURED PERPENDICULAR FROM THE REAR WALL PER
 FBC ACC 604.3.1 AND 604.8.1.1.
 ...C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ...D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ...E) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ...F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ...G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL
 NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER FBC
 ACC 604.4.
 ...H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ...I) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ...J) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ...K) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 3. PLAN SHEET A0.03/PLUMBING FIXTURES/TABLE 403.1 FBC
 PLUMBING: PER WPB FBC 107.2.1, PLEASE CONFIRM THAT THE
 PLUMBING FIXTURES, WHICH ARE ALREADY IN PLACE, IS NOT
 PART OF THE ORIGINAL CALCULATIONS FOR THE EXISTING
 RESTAURANT SPACE.
  
 4. PLAN SHEET P3.01/ WATER HEATER DETAIL: PRV AS PER
 PLUMBING LEGEND SYMBOLS AND ABBREVIATIONS APPEARS TO
 INDICATE A PRESSURE REDUCING VALVE; THE SYMBOL ITSELF
 DOES NOT MATCH. IT IS NOTED THAT THE PRV APPEARS NOT TO
 CONNECT TO THE WATER HEATER. PER WPB FBC 107.2.1,
 CLARIFY; IF THIS IS ACTUALLY A PRESSURE RELIEF VALVE
 THAT DISCHARGES TO THE ATMOSPHERE, PROVIDE A POINT OF
 TERMINATION.
  
 5. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATER.
  
 6. GREASY WASTE: SEE BELOW.
 ...A) THE PLUMBING FIXTURES/EQUIPMENT FOR NEW WORK
 APPEARS TO SERVICE ONLY BEVERAGE CONSUMPTION AND DOES
 NOT SEEM TO INCORPORATE FOOD PREP. PER FBC PL 1003.2,
 WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR. PER WPB FBC 107.2.1, INDICATE ANY EQUIPMENT
 THAT WILL ACTUALLY BE DISCHARGING GREASY WASTE OR OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER,
 WHICH WOULD BE REQUIRED TO DISCHARGE TO AN INTERCEPTOR
 AS REQUIRED BY FBC PL 1003.1. ALL OTHER SHALL DISCHARGE
 DIRECTLY TO THE SANITARY.
 ...B) PER WPB FBC 107.2.1, PROVIDE THE CALCULATIONS FOR
 THE GREASY WASTE ADDED TO THE EXISTING SYSTEM. IT IS
 NOTED ON P2.03 THAT THE EXISTING SYSTEM FULL CAPACITY
 IS 6456 LBS OF GREASE AND THE EXISTING SYSTEM IS AT
 4630 LBS.
  
 7. PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAM(S), CALCULATIONS FOR NEW STORM DRAINS AND
 CLARIFICATIONS AS TO HOW THE NEW ROOF DRAINAGE WILL
 INTEGRATE WITH THE EXISTING STORM WATER SYSTEM(S).
 INCLUDE ANY OVERFLOW, SECONDARY SYSTEMS THAT MAY BE
 REQUIRED. CLEARLY SHOW ALL PIPING, GUTTERS, SCUPPERS,
 DOWNSPOUTS. SHOW COMPLIANCE WITH FBC PL 1106.2 THROUGH
 1106.6 INCLUDING ALL TABLES.
  
 8. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 9. PLAN SHEET P3.01: PER WPB FBC 107.2.1, PLUMBING
 FIXTURE SCHEDULE SHALL COMPLY WITH FLORIDA PLUMBING
 CODE 2020 7TH EDITION
  
 10. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR INDIRECT
 WASTE PIPING FROM SINKS, ICE MAKERS/BINS AND OTHER
 EQUIPMENT TO FLOOR SINK SHOWING COMPLIANCE WITH FBC PL
 802.1.5, 802.1.6 AND 802.1.7.
  
 11. PER FBC FL 1002.4.1, PROVIDE TRAP SEAL PROTECTION
 FOR THE FLOOR DRAIN. PER WPB FBC 107.2.1, PROVIDE A
 TRAP SEAL PROTECTION SPECIFICATION AND DETAIL COMPLYING
 WITH ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2,
 1002.4.1.3 OR 1002.4.1.4.
  
 12. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22010966 185 BANYAN BLVD