2022-02-08 16:06:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF AN ASSEMBLY OCCUPANCY ON A |
| ROOF TOP OF A FIRE SPRINKLERED BUILDING THAT HAS |
| ATTACHED ROOFING/CANOPIES FOR OCCUPANCY UNDER THEM. |
| |
| THE EXISTING FIRE SPRINKLER SYSTEM OF THE BUILDING IS |
| REQUIRED TO BE EXTENDED INTO THE ATTACHED OCCUPIED |
| SPACES. |
| |
| PER NFPA 101CHAPTER 12 |
| |
| 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 12.3.5.1 THE FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE |
| PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 9.7.1.1(1): |
| (1) DANCE HALLS |
| (2) DISCOTHEQUES |
| (3) NIGHTCLUBS |
| (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| |
| PLEASE REVIEW AND PROVIDE FOR FIRE SPRINKLER |
| PROTECTION. |
| |
| |
| 2) THERE IS NO INDICATION OF FIRE ALARM PROTECTION. |
| |
| THERE IS AN EXISTING FIRE ALARM SYSTEM WITHIN THE |
| BUILDING. |
| |
| ANY NOTIFICATION OF THE BUILDING FIRE ALARM SHALL BE |
| EXTENDED FOR PROTECTION OF THIS NEW AREA. |
| |
| PER NFPA 101 CH 12 |
| |
| 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A |
| MULTIPLE OCCUPANCY |
| PROTECTED AS A MIXED OCCUPANCY (SEE 6.1.14) SHALL BE |
| PERMITTED TO BE |
| SERVED BY A COMMON FIRE ALARM SYSTEM, PROVIDED THAT THE |
| INDIVIDUAL |
| REQUIREMENTS OF EACH OCCUPANCY ARE MET. |
| |
| |
| 3) SHEET E 102 - THERE ARE INDICATIONS OF EXITS SIGNS |
| HOWEVER, A REVIEW OF THE EXIT LOCATIONS REQUIRES |
| MODIFICATION AND ADDITION. |
| |
| A) THE EXIT SIGN AT THE WEST END AT THE STAIRWAY DOES |
| NOT APPEAR TO BE VISABLE FROM THE EAST END OF WALKWAY. |
| IT APPEARS THAT IT CAN BE MORE VISABLE MOVED TO THE |
| NORTH. |
| |
| B) THERE IS NO EXIT SIGN IN THE BAR AREA LEADING PEOPLE |
| TO SOUTH STAIRWAY. |
| |
| C) THERE IS NO EXIT SIGN LEADING PEOPLE TO THE SOUTH |
| STIRWAY FROM THE ROUNDED CORNER PRIVATE LOUNGE AREA. |
| |
| D) THE EXIT SIGN AT THE SOUTH STAIRWAY MAY NOT BE |
| VISABLE FROM THE OPEN BAR AREA. |
| |
| |
| |
| 4) SHEETS ELECTRICAL - IT IS NOT CLEAR IF EMERGENCY |
| LIGHTING IS PROVIDED THAT ILLUMINATES THE MEANS OF |
| EGRESS. |
| |
| PER NFPA 12 |
| |
| 12.2.9 EMERGENCY LIGHTING. |
| 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| ACCORDANCE WITH SECTION |
| 7.9. |
| |
| 7.9 EMERGENCY LIGHTING |
| 7.9.1 GENERAL. |
| 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| FOLLOWING: |
| (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| 11 THROUGH 43 |
| (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| ADDRESSED IN |
| SECTION 11.7 |
| (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| OF THIS CODE |
| (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| ENCLOSURES, FOR WHICH |
| THE FOLLOWING ALSO APPLY: |
| (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| INCLUDE A |
| STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| ENCLOSURE |
| MECHANICAL VENTILATION EQUIPMENT. |
| (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| FOR THE |
| STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| SUPPLY. |
| (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN |
| ACCORDANCE |
| WITH 7.2.1.6.2 |
| |
| 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL |
| INCLUDE ONLY DESIGNATED |
| STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND |
| PASSAGEWAYS |
| LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT |
| DISCHARGE SHALL |
| INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES, |
| WALKWAYS, AND ESCALATORS |
| LEADING TO A PUBLIC WAY. |
| |
| PLEASE PROVIDE DETAILS OF THE PRPOSED EMERGENCY |
| LIGHTING MEETING THE REQUIREMENTS. |
| |
| |
| |
| 5) GENERAL INFOMATION - PLEASE PROVIDE DETAILS FOR ANY |
| PROPOSED OPEN FLAME ORNAMENTAL LIGHTING AND/OR PROPANE |
| HEATERS/PROPANE DECORATIVE LIGHTING. |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |