2022-03-15 12:29:13CODES IN EFFECT:
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E101
  
 FOLLOWING CIRCUITS TO BE GFCI PROTECTED PER
 210.8(B)(2-5) 125 VOLT AND UPTO 150 VOLT TO GROUND
 OUTLETS.
 RT1, 2, 3-5, 4 , 6, 7. 8, 9, 10, 11, 12, 14, 15, 16,
 17-19, 21, 27, 29-31,33-35, 37-39, 40
  
 PAGE E201
  
 NEED A LOAD CALCULATION ON THE 800A MAIN, FAULT CURRENT
 FOR THE NEW PANEL, BREAKERS. 215.5, 110.10