Plan Review Notes
Plan Review Notes For Permit 22010957
Permit Number 22010957
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-27 08:19:29JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R26 SELECTED SYSTEM NO. W-103 DO NOT
 MEET THE EXPOSURE CATEGORY D; ZONE 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 3. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE
 CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE D
 (-131.42).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  