2022-08-23 13:46:17 | 8.23.22 REVIEW | | | | 1. SATISFIED - SURVEY PROVIDED. | | | | 2. POWER PULLED FROM LOCATION ALONG ALLEY FRONTAGE, THE | | BULB-OUT IS NOT PART OF THE ALLEY ROW AND POWER SOURCE | | IS LOCATED ON PRIVATE PROPERTY. PLAN SHEETS AND SURVEY | | ALSO SUGGEST PRIVATE PROPERTY, PLEASE PROVIDE OWNERS | | CONSENT OR PROVIDE PROOF OF NECESSARY EASEMENTS TO PULL | | POWER FROM THIS LOCATION. OTHERWISE POWER MUST BE | | OBTAINED FROM ANOTHER SOURCE. | | | | 3. PARTIALLY SATISFIED - POLE ELEVATION SHEET INCLUDED. | | PLEASE PROVIDE PLAN SHEETS OF THE WCF POLE AS WELL AS | | ELECTRIC ROUTE. | | | | 4. PLEASE PROVIDE AN 8FT. BUFFER BETWEEN THE TRUNK OF | | ANY TREES AND PALMS FROM ANY HANDHOLES, BOREPITS, AND | | EXCAVATION WORK. | | | | 5. PLEASE PROVIDE LETTER OF NO RESPONSE FROM UTILITY | | PROVIDERS, SHOULD THERE BE NO RESPONSE TO PREVIOUS | | COMMUNICATIONS. | | | | CHRIS KIMMERLY, AICP | | URBAN DESIGN PLANNER | | 822.1426 [email protected] |
|