2022-02-24 09:04:32 | 02/24/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEETS P1.2 AND P3.1, THE # 7 RISER GOES TO A |
| BATHROOM GROUP AND A KITCHEN. THE KITCHEN SINK CANNOT |
| DISCHARGE INTO THE WET VET OF A BATHROOM GROUP. IT MUST |
| BE DOWNSTREAM PER THE 2020 FBC SECTION R3108.1 |
| HORIZONTAL WET VENT PERMITTED. |
| |
| 2. ON SHEETS P2.1 AND P2.2; |
| |
| A. THE HOT WATER LINES LOOPED FOR THE RECIRCULATING |
| SYSTEM ARE NOT IN A CONTINUOUS LOOP. THERE IS A |
| REQUIREMENT IN THE FLORIDA ENERGY CODE SEC. C404.6.1. |
| THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND |
| THE OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE |
| MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE |
| ACCORDANTLY. IF THERE ARE THREE SEPARATE AREAS OF THE |
| TANK-LESS UNITS, EACH ONE SHALL HAVE ITS OWN RETURN; |
| FEEL FREE TO CONTACT ME TO DISCUSS ACTION ON THE |
| RECIRCULATING SYSTEM. |
| |
| B. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC WATER |
| RISER DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| C. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED |
| IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING |
| OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING. |
| |
| D. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1' |
| AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC R318.5. |
| |
| 3. ON SHEET P4.1; |
| |
| A. IT SHOWS THE SANITARY FOR THE STANDPIPE AS A |
| COMBINATION FITTING THAT CHOCKS THE VENT. WOULD YOU |
| PLEASE CORRECT PER THE 2020 FBC R 3005.1 DRAINAGE |
| FITTINGS AND CONNECTIONS? |
| |
| B. IT SHOWS FOUR TANSLESS IN SERIES, BUT FIVE TOTAL MAY |
| NEED THREE DIFFERENT SYSTEM CONFIGURATIONS PER COMMENT |
| 2 - A. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS |
| TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| REQUEST. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |