Plan Review Notes
Plan Review Notes For Permit 22010949
Permit Number 22010949
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-24 09:04:3202/24/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEETS P1.2 AND P3.1, THE # 7 RISER GOES TO A
 BATHROOM GROUP AND A KITCHEN. THE KITCHEN SINK CANNOT
 DISCHARGE INTO THE WET VET OF A BATHROOM GROUP. IT MUST
 BE DOWNSTREAM PER THE 2020 FBC SECTION R3108.1
 HORIZONTAL WET VENT PERMITTED.
  
 2. ON SHEETS P2.1 AND P2.2;
  
 A. THE HOT WATER LINES LOOPED FOR THE RECIRCULATING
 SYSTEM ARE NOT IN A CONTINUOUS LOOP. THERE IS A
 REQUIREMENT IN THE FLORIDA ENERGY CODE SEC. C404.6.1.
 THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND
 THE OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE
 MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY. IF THERE ARE THREE SEPARATE AREAS OF THE
 TANK-LESS UNITS, EACH ONE SHALL HAVE ITS OWN RETURN;
 FEEL FREE TO CONTACT ME TO DISCUSS ACTION ON THE
 RECIRCULATING SYSTEM.
  
 B. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC WATER
 RISER DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 C. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED
 IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING
 OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING.
  
 D. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1'
 AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC R318.5.
  
 3. ON SHEET P4.1;
  
 A. IT SHOWS THE SANITARY FOR THE STANDPIPE AS A
 COMBINATION FITTING THAT CHOCKS THE VENT. WOULD YOU
 PLEASE CORRECT PER THE 2020 FBC R 3005.1 DRAINAGE
 FITTINGS AND CONNECTIONS?
  
 B. IT SHOWS FOUR TANSLESS IN SERIES, BUT FIVE TOTAL MAY
 NEED THREE DIFFERENT SYSTEM CONFIGURATIONS PER COMMENT
 2 - A. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  