Notes
Date Text
2022-04-13 09:42:29FIRE PROVISO COMMENTS:
  
 THERE ARE INDCIATIONS OF DOORS TO REMIAN UNLOCKED
 DURING OPERATION HOURS PER 7.2.1.5.
  
 HOWEVER, SHOULD THE NEED APPLY TO THESE DOORS OF OTHERS
 WITHIN THIS OCCUPANCY,
  
 PER NFPA 101 CH 38 NEW BUSINESS OCCUPANCY
  
 38.2.2.2.2* DOOR LOCKING TO PREVENT UNWANTED ENTRY.
 WHERE
 APPROVED, DOORS, OTHER THAN THOSE COMPLYING WITH
 38.2.11.2, SHALL BE
 PERMITTED TO BE LOCKED TO PREVENT UNWANTED ENTRY
 PROVIDED THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) THE LOCKING MEANS SHALL BE CAPABLE OF BEING ENGAGED
 WITHOUT
 OPENING THE DOOR.
 (2) THE UNLOCKING AND UNLATCHING OPERATION FROM THE
 EGRESS SIDE OF
 THE DOOR SHALL BE ACCOMPLISHED WITHOUT THE USE OF A
 KEY, TOOL, OR
 SPECIAL KNOWLEDGE OR EFFORT.
 (3) THE RELEASING MECHANISM SHALL OPEN THE DOOR LEAF
 WITH NOT MORE
 THAN ONE RELEASING OPERATION.
 (4) THE RELEASING MECHANISM FOR UNLOCKING AND
 UNLATCHING SHALL BE
 LOCATED AT A HEIGHT NOT LESS THAN 34 IN. (865 MM) AND
 NOT EXCEEDING
 48 IN. (1220 MM) ABOVE THE FINISHED FLOOR.
 (5) LOCKS, IF REMOTELY ENGAGED, SHALL BE UNLOCKABLE
 FROM THE EGRESS
 SIDE OF THE DOOR WITHOUT THE USE OF A KEY, TOOL, OR
 SPECIAL KNOWLEDGE
 OR EFFORT.
 (6) THE DOOR SHALL BE CAPABLE OF BEING UNLOCKED AND
 OPENED FROM
 OUTSIDE THE ROOM WITH THE NECESSARY KEY OR OTHER
 CREDENTIAL.
 (7) THE LOCKING MEANS SHALL NOT MODIFY THE DOOR CLOSER,
 PANIC HARD WARE, OR FIRE EXIT HARDWARE.
 (8) MODIFICATIONS TO REQUIRED FIRE DOOR ASSEMBLIES,
 INCLUDING DOOR
 HARDWARE, SHALL BE IN ACCORDANCE WITH NFPA 80.
  
 A.38.2.2.2.2 THE INTENT OF THIS SECTION IS TO APPLY
 ONLY WHERE SPECIALIZED
 SECURITY MEASURES ARE NEEDED TO PREVENT UNWANTED ENTRY.
 EXAMPLES OF
 DOORS THAT MIGHT USE THESE PROVISIONS INCLUDE COLLEGE
 AND UNIVERSITY
 CLASSROOM DOORS, AREAS OF OFFICE SPACES OPEN TO THE
 PUBLIC, LABORATORIES,
 OR INSTRUCTIONAL ROOMS OR SPACES
  
 BE MINDFUL OF NFPA 101 CH 38
  
 38.2.2.2.3* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON
 PRINCIPAL ENTRANCE/EXIT DOORS.
  
 A.38.2.2.2.3 THE WORDS ?PRINCIPAL ENTRANCE/EXIT DOORS?
 DESCRIBE DOORS
 THAT THE AUTHORITY HAVING JURISDICTION CAN REASONABLY
 EXPECT TO BE
 UNLOCKED IN ORDER FOR THE FACILITY TO DO BUSINESS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL