Date |
Text |
2022-05-02 11:05:13 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| 3.) FBC B 107, THE PLAN AND APPLICATION REFER TO |
| WINDOWS IN SEVERAL AREAS. NO PRODUCT APPROVAL FOR |
| WINDOWS WAS SUBMITTED AND THERE IS NOTHING ON THE |
| OPENING SCHEDULE FOR WINDOWS. IF WINDOWS ARE NOT |
| PROPOSED, SUBMIT A NEW APPLICATION AND PLAN REMOVING |
| WINDOWS FROM SCOPE OF WORK. |
| |
| 4.) FBC B 107, ALL PLAN SHEETS NEED TO BE SIGNED BY THE |
| PERSON TAKING RESPONSIBILITY FOR THE PLAN SHEETS. IF |
| THE PLAN SHEETS ARE FROM SIW WINDOWS & DOORS, AS TITLE |
| BLOCK INDICATES, THEN THE PRINTED NAME & SIGNATURE |
| (INCLUDING SEAL IF ARCHITECT OR ENGINEER IS SIGNING) |
| MUST BE ON EACH PLAN SHEET. IF THERE IS NOT A TITLE |
| BLOCK ON PLANS, THEN IT WILL BE CONSIDERED DESIGNED BY |
| THE INDIVIDUAL THAT PRINTS NAME AND SIGNS NAME, SUCH AS |
| A GENERAL CONTRACTOR. |
| THE (3) PLAN SHEETS NEED TO BE NUMBERED AS A SET OF (3) |
| AS FOLLOWS: |
| |
| PLAN SHEET (LAYOUT-SCHEDULE-ELEVATION) SHOULD BE |
| LABELED 1 OF 3 NOT 1 OF 1. |
| PLAN SHEET (DOOR LAYOUT) SHOULD BE LABELED 2 OF 3 NOT 1 |
| OF 1. |
| PLAN SHEET (DOOR LAYOUT/OCCUPANCY INFORMATION) SHOULD |
| BE LABELED AS IS 3 OF 3. |