Plan Review Notes For Permit 22010940 |
Permit Number |
22010940 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-05 12:04:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE PLAN TO STATE OCCUPANCY CLASSIFICATION, FBC B | | CHAPTER 3. THE APPLICATION STATES THIS IS FOR | | "NORTHWOOD RESIDENCE". THIS IS A COMMERCIAL BUILDING. | | | | 2. SHOW THE ACCESSIBLE ROUTE. COASTAL DOOR HAS THE | | STANDARD THRESHOLD HIGHLIGHTED RATHER THAN THE ADA | | THRESHOLD. COMPLIANCE NOT CLEAR, FBC ACCESSIBLITY. SEE | | DEFINITION OF "ACCESSIBLE ROUTE" IN CHAPTER 2. | | | | 3. FBC 107, THE PLAN AND APPLICATION REFER TO WINDOWS, | | BUT NO WINDOWS SHOWN ON THE PLAN, NO PRODUCT APPROVAL | | SUBMITTED. IF WINDOWS ARE NOT PROPOSED, SUBMIT A NEW | | APPLICATION AND PLAN REMOVING WINDOWS FROM SCOPE. | | | | 4. INCLUDE THE PRINTED NAME AND SIGNATURE OF THE PERSON | | TAKING RESPONSIBILITY FOR THE PLAN, FBC 107. | | | | | | | | |
|