Date Text
2022-03-07 14:01:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF CLOSELY SPACED SIDEWALL
 SPRINKLERS ALONG EACH SIDE OF THE COMMON AREA.
  
 MY UNDERSTANDING WAS THAT THIS CONFIGURATION WAS A
 TEMPORAY INSTALLATION FOR CONSTRUCTION PURPOSES.
  
 IF YOU ARE PROPOSING TO KEEP THIS AS A PERRMANENT
 INSTALLATION PLEASE PROVIDE THE CODE SECTION WITHIN
 NFPA 13 THAT ALLOWS FOR IT.
  
  
 1A) THERE ARE INDICATIONS OF DROPS ALONG THE OUTSIDE
 WALLS OF THE ENTIRE FLOOR THAT APPEAR TO SPACED TOO FAR
 APART AND DO NOT COVER POTENTIAL VOID SPACES.
  
 PLEASE PROVIDE A REVIEW OF THESE AREAS INDICATING THE
 AREAS AND DEPTHS OF VOIDS SHOWING COMPLIANCE WITH THE
 SECTION OF NFPA 13 .
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  