Date |
Text |
2022-03-07 09:37:01 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 22010878 |
| 3/7/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT COMPLETE SPECS FOR THE NEW RANGE THAT SHOW |
| THE TOTAL BTU LOAD AND LISTING OF THE APPLIANCE- SEC. |
| G2447.1 FBC RES. |
| |
| 2) THE SUBMITTED CONTRACT DOES NOT APPEAR TO INCLUDE |
| THE COST OF THE RANGE. TOTAL PERMIT VALUE IS BASED ON |
| COSTS OF LABOR, MATERIAL, EQUIPMENT AND APPLIANCES- |
| SEC. 109.3 WPB. |
| |
| 3) GAS RISER: |
| A) PROVIDE THE TOTAL BTU LOAD OF THE NEW RANGE AND THE |
| TOTAL DEVELOPED LENGTH OF THE SYSTEM- SEC. G2413.4.1 |
| FBC RES. |
| B) SHOW THE INPUT AND OUTPUT GAS PRESSURE AT THE |
| REGULATOR- SEC. G2421.2 FBC RES. |
| |
| 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW |
| RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. |
| G2407.1 FBC RES. |
| |
| 5) CLARIFY- EXISTING OR NEW EXHAUST VENTILATION SYSTEM? |
| PROVIDE DETAILS FOR NEW EXHAUST HOOD AND DUCT |
| INSTALLATIONS- SEE SECS. M1503.1- 1503.4 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |