Plan Review Notes
Plan Review Notes For Permit 22010878
Permit Number 22010878
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-07 09:37:011ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22010878
 3/7/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT COMPLETE SPECS FOR THE NEW RANGE THAT SHOW
 THE TOTAL BTU LOAD AND LISTING OF THE APPLIANCE- SEC.
 G2447.1 FBC RES.
  
 2) THE SUBMITTED CONTRACT DOES NOT APPEAR TO INCLUDE
 THE COST OF THE RANGE. TOTAL PERMIT VALUE IS BASED ON
 COSTS OF LABOR, MATERIAL, EQUIPMENT AND APPLIANCES-
 SEC. 109.3 WPB.
  
 3) GAS RISER:
 A) PROVIDE THE TOTAL BTU LOAD OF THE NEW RANGE AND THE
 TOTAL DEVELOPED LENGTH OF THE SYSTEM- SEC. G2413.4.1
 FBC RES.
 B) SHOW THE INPUT AND OUTPUT GAS PRESSURE AT THE
 REGULATOR- SEC. G2421.2 FBC RES.
  
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC.
 G2407.1 FBC RES.
  
 5) CLARIFY- EXISTING OR NEW EXHAUST VENTILATION SYSTEM?
 PROVIDE DETAILS FOR NEW EXHAUST HOOD AND DUCT
 INSTALLATIONS- SEE SECS. M1503.1- 1503.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  