2022-04-16 15:08:43 | NFIP PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| |
| 2ND REVIEW |
| |
| FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NEW GENERAL COMMENTS: |
| |
| SEE FILE NAMED: PRODUCT APPROVAL-FLOOD VENT IN THE |
| SUPPORTING DOCUMENTS FOR COMMENTS 1 & 2 BELOW: |
| |
| 1. SEPERATE THE ICC-ES REPORT FROM PRODUCT APPROVAL |
| FL15822-R7 AND UPLOAD EACH DOCUMENT SEPERATELY. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 2. PRODUCT APPROVAL FL15822-R7 IS MISSING THE |
| EVALUATION REPORT AND INSTALLATION INSTRUCTIONS. |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| NEW ELEVATION CERTIFICATE COMMENTS: |
| |
| 3. LINE A6. PROVIDE A PHOTOGRAPH OF THE INSTALLED FLOOD |
| VENT MODEL 1540-521 (STACKER). |
| |
| 4. LINE A9. REQUIRED DATA IS THE TOTAL SQUARE INCHES OF |
| THE FLOOD VENTS: THIS SHOULD BE 500 SQ/IN PER TABLE 1 |
| OF THE ICC-ES EVALUATION REPORT. |
| |
| 5. LINE C2 (E). LOWEST ELEVATION OF EQUIPMENT SERVICING |
| THE BUILDING IS THE AIR HANDLER LOCATED IN THE HVAC |
| CLOSET INSIDE THE GARAGE. |
| BOTTOM OF EQUIPMENT SHAL BE AT OR ABOVE THE DFE OF 8.0' |
| NAVD. |
| ENTER THIS INFORMATIUON IN THE COMMENTS AREA OF SECTION |
| D. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |