Plan Review Notes
Plan Review Notes For Permit 22010874
Permit Number 22010874
Review Stop NFIP
Sequence Number 2
Notes
Date Text
2022-04-16 15:08:43NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 2ND REVIEW
  
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NEW GENERAL COMMENTS:
  
 SEE FILE NAMED: PRODUCT APPROVAL-FLOOD VENT IN THE
 SUPPORTING DOCUMENTS FOR COMMENTS 1 & 2 BELOW:
  
 1. SEPERATE THE ICC-ES REPORT FROM PRODUCT APPROVAL
 FL15822-R7 AND UPLOAD EACH DOCUMENT SEPERATELY.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PRODUCT APPROVAL FL15822-R7 IS MISSING THE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NEW ELEVATION CERTIFICATE COMMENTS:
  
 3. LINE A6. PROVIDE A PHOTOGRAPH OF THE INSTALLED FLOOD
 VENT MODEL 1540-521 (STACKER).
  
 4. LINE A9. REQUIRED DATA IS THE TOTAL SQUARE INCHES OF
 THE FLOOD VENTS: THIS SHOULD BE 500 SQ/IN PER TABLE 1
 OF THE ICC-ES EVALUATION REPORT.
  
 5. LINE C2 (E). LOWEST ELEVATION OF EQUIPMENT SERVICING
 THE BUILDING IS THE AIR HANDLER LOCATED IN THE HVAC
 CLOSET INSIDE THE GARAGE.
 BOTTOM OF EQUIPMENT SHAL BE AT OR ABOVE THE DFE OF 8.0'
 NAVD.
 ENTER THIS INFORMATIUON IN THE COMMENTS AREA OF SECTION
 D.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  