2022-02-16 16:58:12 | NFIP PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| |
| 1ST REVIEW |
| |
| FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD |
| HAZARD AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS |
| SITE IS AE WITH A BASE FLOOD ELEVATION (BFE) OF 6.0 |
| NAVD. THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE |
| NO. 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF |
| FREEBOARD. THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT |
| OR ABOVE 8.0 NAVD. |
| |
| 1. THE GARAGE DOOR VENT LETTER SUBMITTED FOR REVIEW BY |
| SCPOTT HAMITON, P.E. REFERENCES NOA 20-0922.19 FOR THE |
| OHD'S. THIS NOA CANNOT BE LOCATED UNDER MASTER PERMIT |
| 19080773. SUBMIT NOA 20-0922.19 FOR REVIEW. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 2. THE GARAGE FLOOD VENT LETTER SUBMITTED FOR REVIEW BY |
| ROGER PATTERSON JANSSEN, P,E, IS TO RE-INSTALL THE |
| FLOOD VENTS TO COMPLY WITH THE REQUIREMENTS OF FEMA'S |
| NFIP TECHNICAL BULLETIN 1. SEE REVISED PLAN PAGE A-1.01 |
| SUBMITTED FOR REVIEW. 2 FLOOD VENTS, MODEL 1540-574, |
| SHALL BE INSTALLED IN OHD #102 AND A STACKER VENT, |
| MODEL 1540-521 WILL BE INSTALLED ON THE SOUTHWEST |
| CORNER OF THE GARAGE. |
| PROVIDE THE PRODUCT APPROVALS, FL5822-R7, FOR MODELS |
| 1540-574 AND 1540-521. INCLUDE THE COVER SHEET, |
| EVALUATION REPORT AND INSTALLATION INSTRUCTIONS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE REFERENCE THE ELEVATION CERTIFICATE FOR THE |
| FOLLWING COMMENTS: |
| |
| 3. A6. PHOTOGRAPHS. THE CERTIFIER MUST PROVIDE AT LEAST |
| 2 PHOTOGRAPHS SHOWING THE FRONT AND REAR OF THE |
| BUILDING TAKEN WITHIN 90 DAYS FROM THE DATE OF |
| CERTIFICATION. PROVIDE A PHOTOGRAPH OF THE FOUNDATION |
| SHOWING A REPRESENTATIVE EXAMPLE OF THE FLOOD OPENINGS |
| OR VENTS. |
| FEMA EC INSTRUCTIONS PAGE 1 OF 9. |
| |
| 4. A7. THE BUILDING DIAGRAM NUMBER IS STATED AS 1B. |
| BASED ON THE FOUNDATION OF THE PROPOSED STRUCTURE, THE |
| BUILDING DIAGRAM NUMBER SHOULD BE 1A. |
| FEMA EC INSTRUCTIONS, PAGE 1 OF 9. |
| |
| 5. A9 B). THE NUMBER OF FLOOD OPENINGS IS STATED AS 4. |
| THERE ARE ONLY 3 FLOOD OPENINGS (1 ON THE SW CORNWER OF |
| THE BUILDING AND 2 IN OHD #102. |
| FEMA EC INSTRUCTIONS, PAGE 2 OF 9. |
| |
| 6. SECTION D - COMMENTS. ITEM #3 REFERENCES FLOOD VENT |
| MODEL: SMART VENT 1540-520. THIS MODEL IS NOT USED FOR |
| THIS PROJECT, IT SHOULD STATE: MODELS 1540-521 AND |
| 1540-574. |
| PROVIDE THE REFERENCED ICC-ES REPORT FOR THE SMART |
| VENTS. |
| PROVIDE THE TOP OF SLAB ELEVATION FOR THE FUTURE |
| GENERATOR SHOWN ON SITE PLAN SP-1.01, UNDER MASTER |
| PERMIT 19080773. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |