2022-02-28 09:39:02 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL5680-R29 HAS BEEN |
| REVISED TO FL5680-R33. PROVIDE THE FOLLOWING: COVER |
| PAGE, EVALUATION REPORTS PAGES 1-6 TO INCLUDE |
| LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. SELECTED SYSTEM NO. W-56 DO NOT MEET |
| EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE |
| REQUIREMENTS. PROVIDE SIGNED AND SEALED ENGINEERED |
| NAILING CALCULATIONS FOR ZONE 3 AS PER LIMITATIONS: |
| 5.7.2./SELECT SYSTEM THAT MEETS OR EXCEEDS EXPOSURE |
| CATEGORY C MINIMUM DESIGN PRESSURE ZONE 3 REQUIREMENTS |
| OF -108.17. |
| 2. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| HEIGHT(S). |
| 3. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF |
| DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE |
| 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020 |
| FBC-PLUMBING |
| 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |