2022-02-14 13:56:06BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW.
  
 REFERENCE THE DESIGN PRESSURE SCHEDULE AND THE ASCE
 7-16 WINDLOAD CHART FOR THE FOLLOWING COMMENT:
  
 1. THE DESIGN PRESSURE OF THE 8FT OHD (48.0/-38.7) DOES
 NOT MEET OR EXCEED THE REQUIRED DESIGN PRESSURE OF THE
 8FT OPENING (38.5/-48.2).
 PROVIDE A PRODUCT APPROVALM THAT MEETS OR EXCEEDS THE
 REQUIRED DESIGN PRESSURES OF THE OPENING (38.5/-48.2).
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  