2022-02-03 12:20:52 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOF COATING TO BE |
| USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND |
| REQUEST. SUBMITTED UNIFLEX LIQUID APPLIED ROOFING |
| SPECIFICATIONS DO NOT MEET THIS REQUIREMENT. |
| 2. FS471. MOISTURE REPORT NOT SIGNED AND SEALED BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| 3. FBC B 107.2.1. PLEASE VERIFY & CORRECT; SUBMITTED |
| ARIEL PHOTO SHOWS WORK PERFORMED @ BUILDING ADDRESS |
| 2520 PRESIDENTIAL WAY, PERMIT APPLICATION IS FOR 2950 |
| PRESIDENTIAL WAY. |
| 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF |
| HEIGHT(S). LOW SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| 5. FBC B 107.2.1 PROPOSED WORK REQUIRES ROOFING |
| CONTRACTORS LICENSE. PLEASE PROVIDE. SECOND REQUEST. |
| PERMIT WILL NOT BE APPROVED OR ISSUED WITHOUT CURRENT |
| ROOFING CONTRACTOR LICENSE. |
| 6. FBC EB 706.1. NOT MORE THAN 25 PERCENT OF THE TOTAL |
| ROOF AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR |
| STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN |
| ANY 12-MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR |
| ROOF SECTION IS REPLACED TO CONFORM TO THIS CODE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |