Plan Review Notes For Permit 22010774 |
Permit Number |
22010774 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-03 09:23:29 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22010774 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE MECHANICAL ENGINEER MUST PROVIDE DRAWINGS | | SHOWING THE REMOVAL OF THE DUCT DETECTORS AND EXPLAIN | | WHY THEY ARE BEING REMOVED ALONG WITH THE | | SPECIFICATIONS OF EACH UNIT SHOWING THE DUCT DETECTORS | | ARE NOT REQUIRED BY FBC M 606. ONCE THESE DRAWINGS HAVE | | BEEN APPROVED THEN THIS PROJECT CAN BE REVISITED. I | | CANNOT COMPLETE THIS REVIEW UNTIL THE MECHANICAL | | DRAWINGS REFLECT THIS DESIGN AND ARE APPROVED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|