2022-02-03 09:23:291ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010774
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL ENGINEER MUST PROVIDE DRAWINGS
 SHOWING THE REMOVAL OF THE DUCT DETECTORS AND EXPLAIN
 WHY THEY ARE BEING REMOVED ALONG WITH THE
 SPECIFICATIONS OF EACH UNIT SHOWING THE DUCT DETECTORS
 ARE NOT REQUIRED BY FBC M 606. ONCE THESE DRAWINGS HAVE
 BEEN APPROVED THEN THIS PROJECT CAN BE REVISITED. I
 CANNOT COMPLETE THIS REVIEW UNTIL THE MECHANICAL
 DRAWINGS REFLECT THIS DESIGN AND ARE APPROVED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  