Plan Review Notes For Permit 22010767 |
Permit Number |
22010767 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-04-07 14:06:50 | PRIVATE PROVIDER PLAN REVIEW AUDIT IS FAILED. | | PLAN REVIEW AUDIT COMMENTS | | | | 1ST AUDIT: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE WIND DESIGN DATA FOR THE WOOD FENCE IS | | INCORRECT. THIS PROJECT IS UNDER THE 2020 FLORIDA | | BUILDING CODE AND ASCE 7-16. THE FENCE IS A RISK | | CATEGORY I WITH A VULT OF 150 MPH. THE EXPOSURE | | CATEGORY IS C. PLEASE CORRECT THE WOOD FENCE | | CALCULATIONS. FBC CITY AMENDMENTS SECTION 120 AND FBC | | 1603.1.4 | | | | |
|