Plan Review Notes For Permit 22010746 |
Permit Number |
22010746 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-07 09:27:50 | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E-WAS-05 SHOWS CONDUIT RUN ALONG WALL IN GEAR ROOM | | IF THIS IS FOR FIRE PUMP IT WILL NEED TO BE INSTALLED | | WITHIN 2" OF CONCRETE. 605.6(A)(2)(D)(1,2) | | | | INSTALLATION SHOWS MORE THAN ONE MEANS OF DISCONNECT | | FOR PUMP 695.4(B)(1) |
|