Plan Review Notes
Plan Review Notes For Permit 22010746
Permit Number 22010746
Review Stop E
Sequence Number 1
Notes
Date Text
2022-02-07 09:27:50 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-WAS-05 SHOWS CONDUIT RUN ALONG WALL IN GEAR ROOM
 IF THIS IS FOR FIRE PUMP IT WILL NEED TO BE INSTALLED
 WITHIN 2" OF CONCRETE. 605.6(A)(2)(D)(1,2)
  
 INSTALLATION SHOWS MORE THAN ONE MEANS OF DISCONNECT
 FOR PUMP 695.4(B)(1)