2022-03-21 13:02:07 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22010709 |
| |
| NOTE: |
| ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 2- FOUNDATION PLAN DOESN'T SPECIFY FOOTING SIZE. |
| ENGINEER OF RECORD NEEDS TO PROVIDE FOOTING DETAIL AND |
| SPECIFICATIONS. SEC. R401.2 FBC-RESIDENTIAL. |
| |
| 3- ROOF FRAMING PLAN DETAIL 2/S3 AND HOUSE BATH SOUTH |
| SIDE VIEW DETAIL 5/S4 ARE INCOMPLETE. ENGINEER OF |
| RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR HAND FRAMED ROOF SYSTEM. SPECIFY TOP RAFTERS |
| SPACING AND STRUCTURAL CONNECTORS, CONNECTION TO 2X8 |
| RIDGE, 2X4 OUTRIGGERS SPACING AND CONNECTORS. NEED TO |
| SPECIFY BOTTOM CHORD OF HAND FRAMED ROOF SYSTEM AND |
| STRUCTURAL CONNECTORS AT EACH END. NEED TO SPECIFY |
| FRAMING AND CONNECTIONS TO EXISTING ROOF. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 4- PROVIDE COMPLETE GABLE END CONSTRUCTION. IS MASONRY |
| OR WOOD FRAMED. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS. SEC. R601.2 FBC-RESIDENTIAL. SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| |
| 5- STRUCTURAL PLANS DON'T SPECIFY TIE BEAM AND LINTEL. |
| ENGINEER NEEDS TO SPECIFY MASONRY TIE BEAM AND WINDOW |
| LINTEL. ALSO, SPECIFY MASONRY REINFORCEMENT AT THE END |
| OF EACH OPENING. SEC. R601.2 FBC-RESIDENTIAL. SEC. |
| R606.10 FBC-RESIDENTIAL. |
| |
| 6- ENGINEER TO SPECIFY ATTACHMENT OF ADDITION TO THE |
| EXISTING BUILDING. SPECIFY CONNECTIONS AT FOOTING, |
| WALLS, ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- TITLE SHEET: |
| REVISE WIND LOAD SCHEDULE: |
| A)COMPONENTS AND CLADDING NEED TO REFERENCE CURRENT |
| ASCE 7-16 NOT ASCE 7-10. REVISE AS REQUIRED. SEC. |
| 553.73 FLORIDA STATUTES. |
| NOTE: UPDATE ROOF LOADS INFORMATION ON ROOF DETAIL PAGE |
| ACCORDINGLY AND ANY OTHER NOTES REFERENCING ASCE 7-10. |
| |
| B)REVISE ROOF AREAS TO MATCH CURRENT ASCE 7-16 AND |
| FIGURE R301.2(7) FBC-RESIDENTIAL REVISED ROOF AREAS. |
| |
| C)REVISE CORNER DISTANCE "A". MINIMUM CORNER DISTANCE |
| "A" IS 4 FEET AS REQUIRED BY FIGURE R301.2(7) |
| FBC-RESIDENTIAL. |
| |
| D)THE "AREA OF COMPONENTS" NEEDS TO BE REVISED. |
| COMPONENTS AND CLADDING LOADS ARE BASED ON THE |
| EFFECTIVE WIND AREA. SEE FOOTNOTE "A" OF TABLE |
| R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| |
| E)REVISE EXTERIOR GLAZED OPENINGS NOTE. CURRENT CODE IS |
| 2020 FBC NOT 2014 FBC. |
| SEC. 553.73 FLORIDA STATUTES. |
| |
| 8- PROVIDE PARTIAL FLOOR PLAN OF EXISTING HOUSE |
| IDENTIFYING ROOM WHERE PROPOSED ADDITION IS GOING TO BE |
| BUILT. NEED TO VERIFY EGRESS COMPLIANCE IF THE ROOM IS |
| A BEDROOM. SEC. R310.2.1 FBC-RESIDENTIAL. ENGINEER OF |
| RECORD NEEDS TO SPECIFY HOW COMPLYING WITH THE EGRESS |
| REQUIREMENTS. |
| |
| 9- PLANS DON'T PROVIDE INFORMATION ABOUT OPENING ON |
| EXISTING MASONRY WALL TO ALLOW FOR NEW BATHROOM DOOR. |
| PROVIDE DETAIL AND SPECIFICATIONS. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 10- DETAIL 5/S4 SPECIFIES 4"X10" ENGINEER BEAM. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THIS BEAM. SEC. |
| R301.2.1 CITY AMENDMENTS. |
| NOTE: COORDINATE WITH ITEM #5 ABOVE. |
| |
| 11- ENGINEER OF RECORD NEEDS TO DEPICT THE BUILDING |
| THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND |
| THEIR R-VALUES. |
| SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| 12- ROOF NEEDS CROSS VENTILATION AS REQUIRED BY SEC. |
| R806.1 FBC-RESIDENTIAL. ENGINEER TO SPECIFY VENT SIZE |
| AND SPACING. |
| |
| 13-WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF |
| RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH |
| SEC. R704 FBC-RESIDENTIAL. |
| |
| 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |