2022-02-16 15:43:01ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL THE REQUIRED RECEPTACLE AT THE KITCHEN
 ISLAND. NEC 210.52(C)(2)
 2) PLEASE DETAIL SMOKE COMBINATION CARBON MONOXIDE
 DETECTORS WITHIN 10? OF EVERY SLEEPING AREA. FBC R315.1
 3) PLEASE DETAIL A NOTE STATING COMPLIANCE WITH NEC
 406.4(D)(5) TAMPER RESISTANT RECEPTACLES
 4) PLEASE DETAIL A NOTE STATING COMPLIANCE WITH NEC
 210.8 GFCI PROTECTION, NEC 210.12 AND NEC 406.4
 ARC-FAULT PROTECTION
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.