Plan Review Notes
Plan Review Notes For Permit 22010598
Permit Number 22010598
Review Stop B
Sequence Number 3
Notes
Date Text
2022-02-24 14:32:14JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED PRODUCT APPROVAL FL5680-R29 HAS BEEN
 REVISED TO FL5680-R33. PROVIDE THE FOLLOWING: COVER
 PAGE, EVALUATION REPORTS PAGES 1-6 TO INCLUDE
 LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. SELECTED SYSTEM NO. W-17 DO NOT MEET
 EXPOSURE CATEGORY D; ZONE 2 & 3 MINIMUM DESIGN PRESSURE
 REQUIREMENTS. PROVIDE SIGNED AND SEALED ENGINEERED
 NAILING CALCULATIONS FOR ZONE 2 & 3 AS PER LIMITATIONS:
 5.7.2. OPTION: REVISE SUBMITTED SIGNED AND SEALED
 ENHANCED NAILING CALCULATIONS TO REFLECT PRODUCT
 APPROVAL FL5680-R33. OPTION: SUBMITTED REVISED DRAWING
 INDICATING FLAT/LOW SLOPE ROOF PITCH OF ??/12 WILL
 SATISFY POSITIVE DRAIN REQUIREMENT OF PREVIOUS COMMENT
 DATED 02/02/2022.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  