2022-02-24 14:32:14 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL5680-R29 HAS BEEN |
| REVISED TO FL5680-R33. PROVIDE THE FOLLOWING: COVER |
| PAGE, EVALUATION REPORTS PAGES 1-6 TO INCLUDE |
| LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. SELECTED SYSTEM NO. W-17 DO NOT MEET |
| EXPOSURE CATEGORY D; ZONE 2 & 3 MINIMUM DESIGN PRESSURE |
| REQUIREMENTS. PROVIDE SIGNED AND SEALED ENGINEERED |
| NAILING CALCULATIONS FOR ZONE 2 & 3 AS PER LIMITATIONS: |
| 5.7.2. OPTION: REVISE SUBMITTED SIGNED AND SEALED |
| ENHANCED NAILING CALCULATIONS TO REFLECT PRODUCT |
| APPROVAL FL5680-R33. OPTION: SUBMITTED REVISED DRAWING |
| INDICATING FLAT/LOW SLOPE ROOF PITCH OF ??/12 WILL |
| SATISFY POSITIVE DRAIN REQUIREMENT OF PREVIOUS COMMENT |
| DATED 02/02/2022. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |