2022-03-25 10:55:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS NO INDICATION NOR DOCUMENTS SUBMITTED FOR |
| THE FIRE SPRINKLER PROTECTION REQUIREMENTS PER F.A.C. |
| 69 A. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| DOCUMENTS. |
| (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S |
| RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| |
| THOUGH A SEPARATE PERMIT FOR THE FIRE SPRINKLER SYSTEM |
| HAS BEEN SUBMITTED, THOSE DOCUMENTS ARE REQUIRED TO BE |
| ATTACHED TO THIS MASTER. |
| |
| |
| |
| 2) THERE ARE INDICATIONS ON THE LIFE SAFETY SHEETS THAT |
| A MANUAL FIRE ALARM IS NOT REQUIRED; HOWEVER, WHERE A |
| FIRE SPRINKLER SYSTEM HAS BEEN INSTALLED IT SHALL BE |
| MONITORED. |
| |
| PER NFPA 101, CH 9 |
| 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| ARE REQUIRED |
| BY ANOTHER SECTION OF THIS CODE, SUPERVISORY |
| ATTACHMENTS SHALL BE |
| INSTALLED AND MONITORED FOR INTEGRITY IN ACCORDANCE |
| WITH NFPA 72 AND |
| A DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO |
| INDICATE A CONDITION |
| THAT WOULD IMPAIR THE SATISFACTORY OPERATION OF THE |
| SPRINKLER SYSTEM. |
| 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| DISPLAYED EITHER AT |
| A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| CONSTANTLY ATTENDED BY QUALI FIED PERSONNEL OR AT AN |
| APPROVED, REMOTELY LOCATED RECEIVING FACILITY. |
| 9.7.2.2 ALARM SIGNAL TRANSMISSION. |
| 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER |
| SYSTEMS IS REQUIRED |
| BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL |
| BE TRANSMITTED |
| TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A |
| REMOTE STATION, A |
| CENTRAL STATION, OR THE FIRE DEPARTMENT |
| 9.7.2.2.2 THE CONNECTION DESCRIBED IN 9.7.2.2.1 SHALL |
| BE IN ACCORDANCE |
| WITH 9.6.1.3. |
| |
| 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL |
| BE INSTALLED, |
| TESTED, AND MAINTAINED IN ACCORDANCE WITH THE |
| APPLICABLE REQUIREMENTS |
| OF NFPA 70 AND NFPA 72 UNLESS IT IS AN APPROVED |
| EXISTING INSTALLATION, |
| WHICH SHALL BE PERMITTED TO BE CONTINUED IN USE. |
| |
| PLEASE REVIEW AND PROVIDE A CLOUDED NOTE OF |
| ACKNOWLEDGMENT ON THESE PAGES. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |