Plan Review Notes
Plan Review Notes For Permit 22010581
Permit Number 22010581
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-03-25 10:55:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION NOR DOCUMENTS SUBMITTED FOR
 THE FIRE SPRINKLER PROTECTION REQUIREMENTS PER F.A.C.
 69 A.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
  
 THOUGH A SEPARATE PERMIT FOR THE FIRE SPRINKLER SYSTEM
 HAS BEEN SUBMITTED, THOSE DOCUMENTS ARE REQUIRED TO BE
 ATTACHED TO THIS MASTER.
  
  
  
 2) THERE ARE INDICATIONS ON THE LIFE SAFETY SHEETS THAT
 A MANUAL FIRE ALARM IS NOT REQUIRED; HOWEVER, WHERE A
 FIRE SPRINKLER SYSTEM HAS BEEN INSTALLED IT SHALL BE
 MONITORED.
  
 PER NFPA 101, CH 9
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED
 BY ANOTHER SECTION OF THIS CODE, SUPERVISORY
 ATTACHMENTS SHALL BE
 INSTALLED AND MONITORED FOR INTEGRITY IN ACCORDANCE
 WITH NFPA 72 AND
 A DISTINCTIVE SUPERVISORY SIGNAL SHALL BE PROVIDED TO
 INDICATE A CONDITION
 THAT WOULD IMPAIR THE SATISFACTORY OPERATION OF THE
 SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY QUALI FIED PERSONNEL OR AT AN
 APPROVED, REMOTELY LOCATED RECEIVING FACILITY.
 9.7.2.2 ALARM SIGNAL TRANSMISSION.
 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER
 SYSTEMS IS REQUIRED
 BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL
 BE TRANSMITTED
 TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A
 REMOTE STATION, A
 CENTRAL STATION, OR THE FIRE DEPARTMENT
 9.7.2.2.2 THE CONNECTION DESCRIBED IN 9.7.2.2.1 SHALL
 BE IN ACCORDANCE
 WITH 9.6.1.3.
  
 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL
 BE INSTALLED,
 TESTED, AND MAINTAINED IN ACCORDANCE WITH THE
 APPLICABLE REQUIREMENTS
 OF NFPA 70 AND NFPA 72 UNLESS IT IS AN APPROVED
 EXISTING INSTALLATION,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN USE.
  
 PLEASE REVIEW AND PROVIDE A CLOUDED NOTE OF
 ACKNOWLEDGMENT ON THESE PAGES.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  