Plan Review Notes
Plan Review Notes For Permit 22010581
Permit Number 22010581
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-29 11:13:461ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC
 LABELS THE SHOWER DRAIN AS WM. PLEASE CORRECT.
  
 2. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE FLOOR PLAN
 ON P2 SHOWS A VENT FOR THE WATER CLOSET AND THE
 ISOMETRIC DOES NOT. PLEASE CORRECT.
  
 3. 2017 WPB AMENDS 107.2.1 - PAGE P3 - ON THE ISOMETRIC
 YOU'VE LABELED THE FIXTURE DRAIN FOR THE WATER CLOSET
 AS 2" AND 3" IS REQUIRED.
  
 4. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC
 APPEARS TO BE MISSING THE WATER LINE FOR THE WATER
 CLOSET IN BATH 3.
  
 5. 2020 FRC P2905.3 - ACCORDING TO THE SCALE ON YOUR
 WATER RISER, IT IS OVER 100 FEET FROM THE TANKLESS TO
 THE FARTHEST FIXTURE. IF THIS IS THE CASE, YOU WILL
 NEED A RECIRCULATING LINE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  