| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC |
| LABELS THE SHOWER DRAIN AS WM. PLEASE CORRECT. |
| |
| 2. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE FLOOR PLAN |
| ON P2 SHOWS A VENT FOR THE WATER CLOSET AND THE |
| ISOMETRIC DOES NOT. PLEASE CORRECT. |
| |
| 3. 2017 WPB AMENDS 107.2.1 - PAGE P3 - ON THE ISOMETRIC |
| YOU'VE LABELED THE FIXTURE DRAIN FOR THE WATER CLOSET |
| AS 2" AND 3" IS REQUIRED. |
| |
| 4. 2017 WPB AMENDS 107.2.1 - PAGE P3 - THE ISOMETRIC |
| APPEARS TO BE MISSING THE WATER LINE FOR THE WATER |
| CLOSET IN BATH 3. |
| |
| 5. 2020 FRC P2905.3 - ACCORDING TO THE SCALE ON YOUR |
| WATER RISER, IT IS OVER 100 FEET FROM THE TANKLESS TO |
| THE FARTHEST FIXTURE. IF THIS IS THE CASE, YOU WILL |
| NEED A RECIRCULATING LINE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |