2022-03-02 13:01:12 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) RESOLVED. [SEE NEW COMMENTS TO #2] |
| |
| 2) [ NOT RESOLVED. THE REVISED LIFE SAFETY PLAN SHOWS A |
| MAXIMUM COMMON PATH OF TRAVEL THAT IS MORE THAN 100 |
| FEET. THEREFORE TWO EXITS FROM THE SPACE ARE REQUIRED. |
| SHOW THE EXIT SEPARATION DISTANCE, THE COMMON PATH OF |
| TRAVEL, TOTAL TRAVEL DISTANCES, EXIT SIGN LOCATIONS, |
| ETC. FOR THE TWO REQUIRED EXITS. FBC CHAPTER 10 ] FBC |
| 1006.2.1 REQUIRES TWO EXITS FROM ANY SPACE THAT EXCEEDS |
| THE OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL |
| DISTANCE VALUES LISTED IN TABLE 1006.2.1. FOR A |
| BUSINESS OCCUPANCY THE MAXIMUM OCCUPANT LOAD IS 49 AND |
| THE MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE IN A |
| FULLY SPRINKLERED BUILDING IS100 FEET. IF THE MAXIMUM |
| COMMON PATH OF EGRESS TRAVEL DISTANCE FROM THE WORK |
| ROOM EXCEEDS 100 FEET ANOTHER EXIT WILL BE REQUIRED. |
| |
| 3) RESOLVED. |
| |
| 4) RESOLVED. |
| |
| 5) RESOLVED. |
| |
| 6) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 7) SHOW HOW THE EXIT ACCESS THROUGH WORKROOM #113 |
| COMPLIES WITH FBC 1016.2 EGRESS THROUGH INTERVENING |
| SPACES. |
| (2) EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE |
| ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H |
| OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS |
| TRAVEL TO AN EXIT. |
| (3) AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT |
| CAN BE LOCKED TO PREVENT EGRESS. |
| |
| 8) THE DOOR FROM WORKROOM #113 TO THE SECOND MEANS OF |
| EGRESS SWINGS OUT INTO A PATH OF EGRESS TRAVEL. FBC |
| 1005.7.1 REQUIRES THAT DOORS IN ANY POSITION SHALL NOT |
| REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF AND |
| WHEN FULLY OPEN SHALL NOT REDUCE THE REQUIRED WIDTH BY |
| MORE THAN 7 INCHES. SHOW THAT THIS DOOR COMPLIES. NOTE: |
| WHEN THE OCCUPANT LOAD IS 50 PERSONS OR LESS FBC |
| 1010.1.2.1 ALLOWS THE DOOR TO SWING AGAINST THE |
| DIRECTION OF EGRESS TRAVEL. THEREFORE, THIS DOOR COULD |
| SWING INTO THE WORKROOM. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |