Plan Review Notes
Plan Review Notes For Permit 22010536
Permit Number 22010536
Review Stop B
Sequence Number 2
Notes
Date Text
2022-03-02 13:01:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED. [SEE NEW COMMENTS TO #2]
  
 2) [ NOT RESOLVED. THE REVISED LIFE SAFETY PLAN SHOWS A
 MAXIMUM COMMON PATH OF TRAVEL THAT IS MORE THAN 100
 FEET. THEREFORE TWO EXITS FROM THE SPACE ARE REQUIRED.
 SHOW THE EXIT SEPARATION DISTANCE, THE COMMON PATH OF
 TRAVEL, TOTAL TRAVEL DISTANCES, EXIT SIGN LOCATIONS,
 ETC. FOR THE TWO REQUIRED EXITS. FBC CHAPTER 10 ] FBC
 1006.2.1 REQUIRES TWO EXITS FROM ANY SPACE THAT EXCEEDS
 THE OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL
 DISTANCE VALUES LISTED IN TABLE 1006.2.1. FOR A
 BUSINESS OCCUPANCY THE MAXIMUM OCCUPANT LOAD IS 49 AND
 THE MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE IN A
 FULLY SPRINKLERED BUILDING IS100 FEET. IF THE MAXIMUM
 COMMON PATH OF EGRESS TRAVEL DISTANCE FROM THE WORK
 ROOM EXCEEDS 100 FEET ANOTHER EXIT WILL BE REQUIRED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 7) SHOW HOW THE EXIT ACCESS THROUGH WORKROOM #113
 COMPLIES WITH FBC 1016.2 EGRESS THROUGH INTERVENING
 SPACES.
 (2) EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 (3) AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT
 CAN BE LOCKED TO PREVENT EGRESS.
  
 8) THE DOOR FROM WORKROOM #113 TO THE SECOND MEANS OF
 EGRESS SWINGS OUT INTO A PATH OF EGRESS TRAVEL. FBC
 1005.7.1 REQUIRES THAT DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF AND
 WHEN FULLY OPEN SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN 7 INCHES. SHOW THAT THIS DOOR COMPLIES. NOTE:
 WHEN THE OCCUPANT LOAD IS 50 PERSONS OR LESS FBC
 1010.1.2.1 ALLOWS THE DOOR TO SWING AGAINST THE
 DIRECTION OF EGRESS TRAVEL. THEREFORE, THIS DOOR COULD
 SWING INTO THE WORKROOM.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  