2022-01-27 16:34:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010536 215 N OLIVE AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. A2.3/DETAIL 18: PER WPB FBC 107.2.1, PROVIDE CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE SINK, SHOWING COMPLIANCE
 WITH FBC ACC 606.2 AND 305.
  
 2. A2.3: PER WPB FBC 107.2.1, SHOW DIMENSIONED KNEE AND
 TOE CLEARANCE FOR THE ACCESSIBLE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH FBC ACC 602.2 AND 306.
  
 3. A2.4/DETAIL 2 AND 5: DETAIL 2 AND 5 SHOW SPACING FOR
 REAR GRAB BAR TO BE 6 INCHES MINIMUM FROM THE SIDE
 WALL. FBC ACC 604.2 REQUIRES THE CENTERLINE OF THE
 WATER CLOSET FROM THE SIDE WALL TO BE 16 INCHES
 MINIMUM/18 INCHES MAXIMUM. PER WPB FBC 107.2.1, SHOW
 THE CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL
 TO BE 16 INCHES MINIMUM/18 INCHES MAXIMUM AND EITHER
 NOTE THE 6 INCHES SPACE AS MAXIMUM OR REMOVE THE
 DIMENSION ENTIRELY. PLEASE SHOW THE WATER CLOSET
 CENTERLINE DIMENSION ON DETAIL 2 AND DETAIL 5.
  
 4. A2.4/DETAIL 5: PER WPB FBC 107.2.1, PROVIDE CLEAR
 FLOOR SPACE FOR THE ACCESSIBLE LAVATORY, SHOWING
 COMPLIANCE WITH FBC ACC 606.2 AND 305.
  
 5. PER WPB FBC 107.2.1 AND FBC PL 310.3, PROVIDE WALL
 FINISH SCHEDULE OR DETAIL FOR THE MOP SINK IN STORAGE
 RM. 115. SHOW COMPLIANCE WITH FBC 1210.2.2.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 4 FEET
 ABOVE THE FLOOR PER FBC-BUILDING SEC. 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET
 THE INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS
 USED FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 6. P0.1 PLUMBING NOTES:
 ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR
 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1,
 CORRECT TO STATE 7TH EDITION.
 ...B) N/A
 ...C) N/A
 ...D) N/A
 ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE
 VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH
 THE ROOF. PER WPB FBC 107.2.1, CLARIFY. IS IT THE
 INTENT THAT ONE OF THE TWO NOTES ALLOW AIR ADMITTANCE
 VALVES/STUDOR VENTS FOR INDIVIDUAL/BRANCH VENTS? PLEASE
 NOTE THAT PER FBC PL 904.1, THE VENT SYSTEM SERVING
 EACH BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT
 PIPE THAT EXTENDS TO THE OUTDOORS. PRIOR TO INSPECTION,
 A PLAN REVISION REFLECTING ANY ACTUAL USE OF AIR
 ADMITTANCE VALVES/STUDOR VENTS SHALL BE SUBMITTED TO
 THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC
 107.2.1.
 ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT.
 PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE
 IT.
 ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?ALL
 COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD
 FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.?
  
 7. P0.1 SANITARY RISER DIAGRAM:
 ...A) IT APPEARS THAT THE INDIVIDUAL VENT FOR THE MOP
 SINK VENTS THROUGH THE ROOF AND THE BRANCH VENTS FROM
 OTHER FIXTURES CONNECT TO IT. HOWEVER, THE SYMBOL FOR
 VTR IS BELOW THE CONNECTION POINT. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
 ...B) PER WPB FBC 107.2.3, PLEASE CLARIFY THAT THE VENT
 FOR THE BATHROOM GROUPS IS A VENT THROUGH THE ROOF. A
 VTR SYMBOL WOULD BE HELPFUL.
  
 8. P0.1 WATER RISER:
 ...A) PER WPB FBC 107.2.1, PROVIDE SCHEMATIC DETAIL FOR
 THE DISHWASHER/SINK/ IWH TO INCLUDE VALVES AND WATER
 HAMMER ARRESTOR (SEE FBC PL 604.9).
 ...B) PER WPB FBC 107.2.1, CONFIRM THAT THE WATER
 HAMMER ARRESTOR PLACEMENT FOR THE SALES KITCHEN
 ADEQUATELY SERVICES THE COLD WATER MAKE UP TO THE
 REFRIGERATOR AND FREEZER ICEMAKERS. IF NECESSARY, PLACE
 THEM IN A MORE SUITABLE LOCATION FOR THE TWO
 CONNECTIONS.
  
 9. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER
 SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND
 STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW
 PREVENTERS SHALL BE LEAD FREE.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 11. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE
 DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE
 WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL
 CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOP.
  
 12. PER WPB FBC 107.2.1, PROVIDE SCHEDULE/SPECIFICATION
 FOR THE CONDENSATE PUMP.
  
 13. P2.0: PER WPB FBC 107.2.1, NOTE SIZING OF
 CONDENSATE DRAINS.
  
 14. P2.0: PER WPB FBC 107.2.1, NOTE DESIGNATED AHU AT
 EACH CONDENSATE PIPING CONNECTION.
  
 15. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT
 REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON
 THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED
 IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY
 ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION.
  
 16. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION
 SIZE
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  