2022-01-27 16:34:01 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22010536 215 N OLIVE AVE |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 1. A2.3/DETAIL 18: PER WPB FBC 107.2.1, PROVIDE CLEAR |
| FLOOR SPACE FOR THE ACCESSIBLE SINK, SHOWING COMPLIANCE |
| WITH FBC ACC 606.2 AND 305. |
| |
| 2. A2.3: PER WPB FBC 107.2.1, SHOW DIMENSIONED KNEE AND |
| TOE CLEARANCE FOR THE ACCESSIBLE DRINKING FOUNTAIN |
| SHOWING COMPLIANCE WITH FBC ACC 602.2 AND 306. |
| |
| 3. A2.4/DETAIL 2 AND 5: DETAIL 2 AND 5 SHOW SPACING FOR |
| REAR GRAB BAR TO BE 6 INCHES MINIMUM FROM THE SIDE |
| WALL. FBC ACC 604.2 REQUIRES THE CENTERLINE OF THE |
| WATER CLOSET FROM THE SIDE WALL TO BE 16 INCHES |
| MINIMUM/18 INCHES MAXIMUM. PER WPB FBC 107.2.1, SHOW |
| THE CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL |
| TO BE 16 INCHES MINIMUM/18 INCHES MAXIMUM AND EITHER |
| NOTE THE 6 INCHES SPACE AS MAXIMUM OR REMOVE THE |
| DIMENSION ENTIRELY. PLEASE SHOW THE WATER CLOSET |
| CENTERLINE DIMENSION ON DETAIL 2 AND DETAIL 5. |
| |
| 4. A2.4/DETAIL 5: PER WPB FBC 107.2.1, PROVIDE CLEAR |
| FLOOR SPACE FOR THE ACCESSIBLE LAVATORY, SHOWING |
| COMPLIANCE WITH FBC ACC 606.2 AND 305. |
| |
| 5. PER WPB FBC 107.2.1 AND FBC PL 310.3, PROVIDE WALL |
| FINISH SCHEDULE OR DETAIL FOR THE MOP SINK IN STORAGE |
| RM. 115. SHOW COMPLIANCE WITH FBC 1210.2.2. |
| WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NON-ABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 4 FEET |
| ABOVE THE FLOOR PER FBC-BUILDING SEC. 1210.2.2. SECTION |
| 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE |
| INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL |
| SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH |
| THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT |
| READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN |
| WHERE COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET |
| THE INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS |
| USED FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS |
| REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS, |
| LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS |
| STEEL. |
| |
| 6. P0.1 PLUMBING NOTES: |
| ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR |
| 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1, |
| CORRECT TO STATE 7TH EDITION. |
| ...B) N/A |
| ...C) N/A |
| ...D) N/A |
| ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE |
| VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH |
| THE ROOF. PER WPB FBC 107.2.1, CLARIFY. IS IT THE |
| INTENT THAT ONE OF THE TWO NOTES ALLOW AIR ADMITTANCE |
| VALVES/STUDOR VENTS FOR INDIVIDUAL/BRANCH VENTS? PLEASE |
| NOTE THAT PER FBC PL 904.1, THE VENT SYSTEM SERVING |
| EACH BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT |
| PIPE THAT EXTENDS TO THE OUTDOORS. PRIOR TO INSPECTION, |
| A PLAN REVISION REFLECTING ANY ACTUAL USE OF AIR |
| ADMITTANCE VALVES/STUDOR VENTS SHALL BE SUBMITTED TO |
| THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC |
| 107.2.1. |
| ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT. |
| PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE |
| IT. |
| ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?ALL |
| COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD |
| FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.? |
| |
| 7. P0.1 SANITARY RISER DIAGRAM: |
| ...A) IT APPEARS THAT THE INDIVIDUAL VENT FOR THE MOP |
| SINK VENTS THROUGH THE ROOF AND THE BRANCH VENTS FROM |
| OTHER FIXTURES CONNECT TO IT. HOWEVER, THE SYMBOL FOR |
| VTR IS BELOW THE CONNECTION POINT. PER WPB FBC 107.2.1, |
| PLEASE CLARIFY. |
| ...B) PER WPB FBC 107.2.3, PLEASE CLARIFY THAT THE VENT |
| FOR THE BATHROOM GROUPS IS A VENT THROUGH THE ROOF. A |
| VTR SYMBOL WOULD BE HELPFUL. |
| |
| 8. P0.1 WATER RISER: |
| ...A) PER WPB FBC 107.2.1, PROVIDE SCHEMATIC DETAIL FOR |
| THE DISHWASHER/SINK/ IWH TO INCLUDE VALVES AND WATER |
| HAMMER ARRESTOR (SEE FBC PL 604.9). |
| ...B) PER WPB FBC 107.2.1, CONFIRM THAT THE WATER |
| HAMMER ARRESTOR PLACEMENT FOR THE SALES KITCHEN |
| ADEQUATELY SERVICES THE COLD WATER MAKE UP TO THE |
| REFRIGERATOR AND FREEZER ICEMAKERS. IF NECESSARY, PLACE |
| THEM IN A MORE SUITABLE LOCATION FOR THE TWO |
| CONNECTIONS. |
| |
| 9. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER |
| SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND |
| STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW |
| PREVENTERS SHALL BE LEAD FREE. |
| |
| 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 11. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE |
| DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE |
| WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL |
| CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE |
| TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE |
| DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR |
| THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF |
| A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER |
| TOP. |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE SCHEDULE/SPECIFICATION |
| FOR THE CONDENSATE PUMP. |
| |
| 13. P2.0: PER WPB FBC 107.2.1, NOTE SIZING OF |
| CONDENSATE DRAINS. |
| |
| 14. P2.0: PER WPB FBC 107.2.1, NOTE DESIGNATED AHU AT |
| EACH CONDENSATE PIPING CONNECTION. |
| |
| 15. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT |
| REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON |
| THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED |
| IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY |
| ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE |
| SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| INSPECTION. |
| |
| 16. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE |
| CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION |
| SIZE |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |