2022-01-26 16:44:18 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22010536 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR THIS TENANT SPACE. FBC EC C403.2.1 |
| |
| 2) THE OUTDOOR AIR CALCULATIONS DOES NOT PROVIDE |
| CALCULATIONS FOR THE RECEPTION AREA OR THE STORAGE |
| AREA, THE CORRIDOR OR THE KITCHENETTE/COPY ROOM. PLEASE |
| PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR EACH |
| USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1 AND |
| TABLE 403.3.1.1 |
| |
| 3) PLEASE SHOW THE ANCHORING OF THE CONDENSING UNITS. |
| FBC 107.2.1 |
| |
| 4) PLEASE EXPLAIN WHY THE BATH EXHAUST IS |
| NON-FUNCTIONING IS THE SALES MASTER BATH. |
| |
| 5) IS THE SALES KITCHEN A FUNCTIONING KITCHEN? IF SO, |
| IS THERE A HOOD ABOVE THE RANGE? |
| |
| 6) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| TERMINATION LOCATION. FBC M 307 |
| |
| 7) PLEASE SHOW THAT THE NEW CONDENSING UNITS WILL MEET |
| THE CLEARANCES FROM THE ROOF EDGE IN FBC M 304.11 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |