Plan Review Notes
Plan Review Notes For Permit 22010535
Permit Number 22010535
Review Stop G
Sequence Number 2
Notes
Date Text
2022-02-16 06:48:2002/16/22 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ISOMETRIC DOES NOT SHOW THE SOURCE OF SUPPLY
 AND THIS IS AN LP TANK; PLEASE SHOW THE LP TANK BEING
 USED AND DIRECTION OF PIPES PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. WOULD YOU PLEASE SHOW WHAT IS NEW AND EXISTING PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 3. THE CITY OF WEST PALM BEACH HAS A PERMIT (07030314)
 ON FILE FOR THE GENERATOR, AND IT IS NOT SHOWN ON THE
 SYSTEM OR NOTE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 5. THE TOTAL BTU LOAD FOR THE SYSTEM IS INCORRECT. THE
 EXISTING GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD
 TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM IF UNDERSIZED. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE, AND THE TYPE OF PIPE TO EACH APPLIANCE.
  
 6. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE PRESSURE MAY REQUIRE A REGULATOR FOR THIS UNIT
 AS PER THE MANUFACTURER'S SPECIFICATION. SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1.
  
 7. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE FOR THE TANKLESS PER THE
 2020 FBC RES. SEC G2421.2.
  
 9. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON
 GAS ISOMERIC FOR THE TANKLESS PER THE 2020 FBC RES.
 SEC. G2420.5.
  
 10. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON
 TANKLESS 2020 FBC RES. SEC. G2419.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  