Plan Review Notes
Plan Review Notes For Permit 22010520
Permit Number 22010520
Review Stop G
Sequence Number 1
Notes
Date Text
2022-01-18 07:33:0501/18/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR GAS TANKLESS AND STOVE EQUIPMENT TO VERIFY
 COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 2. WOULD YOU PLEASE SUBMIT THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON ISOMETRIC
 LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER
 STANDARD THAT WAS USED IN THE DESIGN OF THIS SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.3.
  
 3. WOULD YOU PLEASE SHOW THE ISOMETRIC DRAWING THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 4. WOULD YOU PLEASE SHOW THE TOTAL BTU LOAD ON THE
 SYSTEM PER THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 5. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2 2020 FBC RES. SEC. G2413.4.1.
  
 6. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY
 PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC.
 402.2 OR 2020 FBC RES. SEC. G2413.2.
  
 7. PROVIDE INFORMATION FOR THE TERMINATION LOCATION OF
 THE EXHAUST VENT. THE EXIT TERMINAL OF A MECHANICAL
 DRAFT SYSTEM (IF INSTALLED) SHALL COMPLY WITH 2020 FBC
 FG SECS. 503.3.3, (1-6), 503.8 (1) (2).
  
 8. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. IF APPLICABLE.
  
 9. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 10. THE TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 11. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES.
 SEC G2421.2.
  
 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE
 ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5. THE
 SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT MOVING THE
 EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS.
  
 13. DRIP LEG IS MISSING ON TANKLESS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 14. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE.
  
 16. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM
 THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF
 APPLICABLE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  