Plan Review Notes
Plan Review Notes For Permit 22010486
Permit Number 22010486
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-03 11:17:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010486 1400 CENTREPARK BLVD # 500
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. A-4/DETAIL 4: PER FBC ACC 603.3, MIRRORS LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB FBC
 107.2.1, PLEASE REVISE TO CLARIFY THE SAME.
  
 2. A-4/DETAIL 1 AND 2: ACCESSIBLE URINALS SHALL BE THE
 STALL-TYPE OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 605.2. PER WPB FBC 107.2.1, PROVIDE DETAIL.
  
 3. PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. PER WPB FBC 107.2.1, PROVIDE NOTE.
  
 4. A-2 AND A-11: PER WPB FBC 107.2.1, PROVIDE CLEAR
 FLOOR SPACE FOR SINK IN CAF? RM 512 COMPLYING WITH FBC
 ACC 305 POSITIONED FOR A FORWARD APPROACH AND CENTERED
 ON THE UNIT.
  
 5. PER WPB FBC 107.2.1, PROVIDE LOCATION OF DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH FBC PL 403.1, TABLE
 403.1 AND 403.5. IF THERE ARE NONE, PROVIDE DRINKING
 FOUNTAIN(S) COMPLYING WITH FBC PL 410.3, FBC ACC 211.2
 AND 602.1 THROUGH 602.6 AND 602.7.
  
 6. PER WPB FBC 107.2.1, PROVIDE LOCATION OF SERVICE
 SINK SHOWING COMPLIANCE WITH FBC PL TABLE 403.1.
  
 7. P0.1/PLUMBING FIXTURE SCHEDULE SPECIFIES NEW WALL
 HUNG WATER CLOSETS (TAG HWC); THE SANITARY RISER
 DIAGRAM INDICATES FLOOR MOUNTED. PER WPB FBC 107.2.1,
 CLEARLY SHOW ON THE RISER DIAGRAM THE CARRIER ASSEMBLY
 AND VENTING. RECONCILE P2.1 WITH REVISED RISER DIAGRAM.
  
 8. P0.1 PLUMBING NOTES:
 ...A) NOTES 1, 11,24,25 ALL REFER TO 6TH EDITION FOR
 2020 FLORIDA BUILDING CODES. PER WPB FBC 107.2.1,
 CORRECT TO STATE 7TH EDITION.
 ...B) NOTE 11 CALLS FOR TYPE L COPPER FOR WATER
 DISTRIBUTION PIPE BUT ALLOWS ALTERNATE MATERIALS. PRIOR
 TO INSPECTION, A PLAN REVISION REFLECTING THE ACTUAL
 MATERIAL SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT,
 APPROVED AND ON SITE. WPB FBC 107.2.1.
 ...C) NOTE 12 CALLS FOR CAST IRON OR PVC FOR THE
 SANITARY PIPING. PRIOR TO INSPECTION, A PLAN REVISION
 REFLECTING THE ACTUAL MATERIAL SHALL BE SUBMITTED TO
 THE BUILDING DEPARTMENT, APPROVED AND ON SITE. WPB FBC
 107.2.1.
 ...D) NOTE 24 CALLS FOR TYPE L COPPER WITH ARMAFLEX
 INSULATION FOR CONDENSATE PIPING THEN ALLOWS PVC WITH
 INSULATION IN RETURN AIR PLENUMS. PER WPB FBC 107.2.1,
 CLARIFY. ADDITIONALLY, PROVIDE THE FIRE/SMOKE RATING
 FOR THE INSULATION. PRIOR TO INSPECTION, A PLAN
 REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE
 SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON
 SITE. WPB FBC 107.2.1.
 ...E) NOTES 26 AND 28: BOTH ALLOW USE OF AIR ADMITTANCE
 VALVES/STUDOR VENTS TO BE USED FOR VENT PIPING THROUGH
 THE ROOF.
 ......1) PLEASE NOTE; FBC PL 918.3.1 REQUIRES AIR
 ADMITTANCE VALVES ARE LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE SCOPE OF WORK IS ON THE
 5TH FLOOR OF A 10 STORY BUILDING. PER WPB FBC 107.2.1,
 CLARIFY. IS IT THE INTENT THAT ONE OF THE TWO NOTES
 ALLOW AIR ADMITTANCE VALVES/STUDOR VENTS FOR
 INDIVIDUAL/BRANCH VENTS? PRIOR TO INSPECTION, A PLAN
 REVISION REFLECTING ANY ACTUAL USE OF AIR ADMITTANCE
 VALVES/STUDOR VENTS SHALL BE SUBMITTED TO THE BUILDING
 DEPARTMENT, APPROVED AND ON SITE. WPB FBC 107.2.1.
 ...F) NOTE 33 SEEMS TO HAVE NO BEARING ON THE PROJECT.
 PER WPB FBC 107.2.1, IF THIS IS THE CASE, PLEASE DELETE
 IT.
 ...G) PER WPB FBC 107.2.1, PROVIDE NOTE STATING "ALL
 COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE LEAD
 FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1."
  
 9. P0.1 WATER RISER: PER WPB FBC 107.2.1, PROVIDE
 SCHEMATIC DETAIL FOR THE DISHWASHER/SINK/ IWH TO
 INCLUDE VALVES AND WATER HAMMER ARRESTOR (SEE FBC PL
 604.9).
  
 10. PER WPB FBC 107.2.1, PROVIDE A BACKFLOW PREVENTER
 SCHEDULE AND SPECIFY BACKFLOW PREVENTER TYPE AND
 STANDARD (ASSE, ASME ETC.). PROVIDE NOTE, BACKFLOW
 PREVENTERS SHALL BE LEAD FREE.
  
 11. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 12. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE
 DISHWASHER SHOWING COMPLIANCE WITH FBC PL 409.4. THE
 WASTE CONNECTION OF A RESIDENTIAL DISHWASHER SHALL
 CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOP.
  
 13. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR ANY EQUIPMENT
 REQUIRING A PLUMBING CONNECTION THAT IS NOT LISTED ON
 THE PLUMBING FIXTURE SCHEDULE. IF THESE MAY BE DEFERRED
 IN ACCORDANCE WITH WPB FBC 107.3.4.2 AS LONG AS THEY
 ARE LISTED ON THE PLANS. SAID DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION.
  
 15. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 CONNECTION SCHEDULE; DFU/TRAP SIZE AND WSFU/CONNECTION
 SIZE
  
 16. P2.1/FLOOR DRAIN FOR ICEMAKER
 ...A) WASTE RECEPTORS SHALL NOT BE INSTALLED IN
 CONCEALED SPACES. READY ACCESS SHALL BE PROVIDED TO
 WASTE RECEPTORS PER FBC PL 802.4. PER WPB FBC 107.2.1,
 SHOW COMPLIANCE.
 ...B) PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR TRAP PRIMER
 ...C) PER WPB FBC 107.2.1, PROVIDE DETAIL OF FLOOR
 DRAIN AND ICE MAKER DISCHARGE WITH AIR GAP
  
 17. PER WPB FBC 107.2.1, PROVIDE AC CONDENSATE PIPE
 ROUTING AND SIZES. COMPLY WITH THE REQUIREMENTS OF FBC
 PL 314.
  
 18. P0.1/WATER RISER: PER WPB FBC 107.2.1, CORRECTLY
 IDENTIFY SK-2.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  