Plan Review Notes
Plan Review Notes For Permit 22010439
Permit Number 22010439
Review Stop E
Sequence Number 1
Notes
Date Text
2022-02-14 09:26:34FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS EXISTING 2/0 CONDUCTORS THAT ARE IN
 VIOLATION OF 310.15(B)(7)(2) MUST BE 3/0 PER CHIEF
 ELECTRICAL INSPECTOR. DOES NOT FEED ENTIRE LOAD AS
 STATED IN SECTION.