2022-02-17 15:22:56ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM SHOWS 2/0 CU WIRE FROM ATS TO PANELS.
 THIS CONDUCTOR MUST HAVE A 100% AMPACITY FOR A 200-AMP
 PANEL. IT IS NOT SUBJECT TO THE 83% ADJUSTMENT AS IT
 DOES NOT CARRY THE ENTIRE LOAD FROM THE SERVICE AS PER
 310.15(B)(7)(1)
  
 FOR A SERVICE RATED 100 THROUGH 400 AMPERES, THE
 SERVICE
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ON EFAMILY
 DWELLING, OR THE SERVICE CONDUCTORS SUPPLYING THE
 ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING UNIT
 IN
 A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED
 TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT OF THE
 SERVICE
 RATING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved