Plan Review Notes For Permit 22010340 |
Permit Number |
22010340 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-25 14:31:53 | RESIDENTIAL(R3) DOOR REPLACEMENT, BUILDING REVIEW | | COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22010340 | | | | NOTE: | | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. | | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL | | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN | | THE FLORIDA BUILDING CODE. | | | | 1-ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS | | BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE "B". | | REVISE ENGINEER'S DESIGN PRESSURES SUBMITTED. | | | | 2-ENGINEER'S DESIGN PRESSURES SUBMITTED NEED ENGINEER'S | | ORIGINAL SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. | | WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. | | NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH | | ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY WITH | | ENGINEER'S ORIGINAL SEAL AND SIGNATURE. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|