2022-01-20 11:15:04 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22010313 |
| 1/20/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1: BASED ON SEC. 454.1.6.1 EXCEPTION FBC B |
| SANITARY FACILITIES FOR THE POOL ARE REQUIRED. THE |
| EXCEPTION TO NOT PROVIDE IS FOR RESIDENTIAL DWELLING |
| UNITS. NOVUS MEDICAL IS CLASSIFIED AS AN I-1 OCCUPANCY |
| BASED ON SEC. 308.3 FBC B AND THE APPROVED BUILDING |
| PLANS UNDER PERMIT 16080844. PLEASE REFER TO SHEET |
| LS-1-101 WHICH INDICATES A MIXED USE OF OUTPATIENT |
| CLINIC AND SLEEPING UNITS. PLEASE PROVIDE SANITARY |
| FACILITIES IN ACCORDANCE WITH TABLE 454.1.6.1 FBC B. |
| |
| 2) SHEET 1: THE AMERCIANS W/ DISABILITIES ACT NOTE ON |
| THE PLAN REFERENCING "PRIVATE RESIDENTIAL COMMUNITY |
| POOL", AND BOAF DECLARATORY STATEMENT DS 2013-011 DOES |
| NOT APPEAR TO BE APPLICABLE TO I-1 OCCUPANCIES. SEE |
| COMMENT #1 ABOVE AND REFER TO SEC. 242.2 FBC ACC |
| SWIMMING POOLS. A POOL LIFT COMPLYING WITH SEC.1009.2 |
| FBC ACC IS REQUIRED. PLEASE REVISE THE PLANS TO SHOW |
| THE LOCATION OF THE LIFT AND PROVIDE INSTALLATION |
| DETAILS. |
| |
| SEC. 242.2 AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL |
| BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF |
| ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING WITH |
| 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER |
| WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING |
| WITH 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT |
| LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL |
| COMPLY WITH 1009.2 OR 1009.3. |
| EXCEPTION 1.WHERE A SWIMMING POOL HAS LESS THAN 300 |
| LINEAR FEET OF SWIMMING POOL WALL, NO MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED |
| THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL |
| LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING |
| WITH 1009.3. |
| PLEASE REFER TO FL. STATUTE 514.0115 FOR ADDITIONAL |
| INFORMATION REGARDING THE USE OF THE POOL. |
| |
| 3) SHEET 1: CLARIFY HOW THE DESIGN BATHING LOAD OF 20 |
| PERSONS WAS DETERMINED. PROVIDE THE CALCULATION AND |
| DESIGN STANDARD USED- SEC. 107.2.1 WPB. |
| |
| 4) SHEET 1: CONCERNING THE IRRIGATION SYSTEM FOR THE |
| AREAS AROUND THE POOL PLEASE REFER TO FAC 64 E-9.004 |
| AND INDICATE HOW COMPLIANCE WILL BE MET: |
| LANDSCAPE IRRIGATION WATER THAT WETS THE WET DECK AREA |
| OF THE POOL, THE POOL ITSELF, ENTERS THE COLLECTOR |
| TANK, OR WETS AN INTERACTIVE WATER FEATURE MUST BE |
| POTABLE WATER FROM A PUBLIC WATER SYSTEM OR SHALL MEET |
| THE BACTERIOLOGICAL QUALITY OF POTABLE WATER AS |
| EVIDENCED BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO |
| THE DEPARTMENT. RECLAIMED WATER MAY NOT BE USED IN |
| THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY |
| OF THE POOL (INSIDE OF THE POOL FENCE OR WITHIN 100 |
| FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP |
| IRRIGATION OR SOAKER HOSES. SIGNS SHALL BE POSTED |
| NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE, |
| AND IS NOT TO BE CONSUMED. |
| |
| 5) SHEET 2: THE HYDRAULIC DESIGN DATA INDICATES THE 5.3 |
| FPS DESIGN VELOCITY OF THE SKIMMER EXCEEDS THE MINIMUM |
| 3.0 FPS- SEC. 454.1.6.5.8 FBC B. |
| |
| 6) SHEET 2 & 3: IT APPEARS THE 3-INCH SKIMMER LINE |
| BRANCH CONNECTING TO THE MAIN IS MISLABELED AS 3-INCH |
| AND NOT 2-INCH BASED ON THE NOTE ON THE PLAN. PLEASE |
| SHOW THE BRANCH LINE SIZE IN THE SKIMMER DETAIL- SEC. |
| 107.2.1 WPB. |
| |
| 7) SHEET 3: PROVIDE AN EQUALIZER LINE DETAIL- SEC. |
| 454.1.6.5.3.2.3 FBC B. |
| |
| 8) SHEETS 4: WASTEWATER FROM THE POOL AND THE COLLECTOR |
| TANK SHALL BE DECHLORINATED AND DISCHARGED THROUGH AN |
| AIR GAP IN THE INTO THE STORM DRAINAGE SYSTEM- SEC. |
| 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF ORDINANCES. |
| THE WASTEWATER SHALL NOT DISCHARGE INTO THE SANITARY |
| SYSTEM AA INDICATED IN NOTE #10. PLEASE REVIEW WPB |
| BUILDING DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE |
| ENGINEER OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM |
| ON THE PLAN AND PROVIDE SPECIFICATIONS FOR ALL |
| EQUIPMENT. PLEASE SEE GUIDELINES BELOW- |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 10) SHEETS 2, 3 & 4: SUBMIT MANUFACTURER'S SPECS FOR |
| THE PUMP AND INCLUDE THE PUMP CURVE- SEC. 454.1.6.5.4 |
| FBC B. |
| |
| 11) SHEETS 2, 3 & 4: SUBMIT MANUFACTURER'S SPECS OR THE |
| FILTER- SEC. 454.1.6.5.5. FBC B. |
| |
| 12) SHEETS 2, 3 & 4: SUBMIT SPECS FOR THE MAIN DRAIN |
| ASSEMBLY INCLUDING THE DRAIN COVER- SEC. |
| 454.1.6.5.10.2, AND THE COLLECTOR TANK- SEC. |
| 454.1.6.5.10.5 FBC B. |
| |
| 13) SHEETS 2, 3 & 4: PROVIDE A CLEANING SYSTEM FOR THE |
| POOL IN ACCORDANCE WITH SEC. 454.1.6.5.12 FBC B. PLEASE |
| NOTE A PORTABLE, ROBOTIC OR PLUMBED-IN VACUUM CLEANING |
| SYSTEM SHALL BE PROVIDED. |
| |
| 14) SEPARATE PERMITS ARE REQUIRED FOR THE WATER SUPPLY |
| LINE AND MAKEUP WATER CONTROL DEVICE, AND THE WATER |
| SUPPLY LINE BACKFLOW PREVENTER- SEC. 105.1 & 10-7.2.1 |
| WPB. PLEASE PLACE NOTES ON THE PLAN TO CLARIFY. |
| |
| A FL. LICENSED PLUMBING CONTRACTORS SHALL OBTAIN A |
| SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| PREVENTER IN ACCORDANCE WITH SECTION 105.1WPB AND SEC. |
| 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 15) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| SECTIONS FROM THE FBC EC: |
| C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS |
| SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF |
| SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED |
| ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND |
| WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH |
| SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER |
| THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A |
| CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED |
| HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING |
| IGNITION PILOTS. |
| C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL |
| METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS |
| AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE |
| INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP |
| MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN |
| COMPLIANCE WITH THIS SECTION. |
| EXCEPTIONS: |
| 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP |
| OPERATION. |
| 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY |
| POOL HEATING SYSTEMS. |
| C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND |
| OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A |
| VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |