2022-06-29 16:55:32 | DRYER EXHAUST DUCT SHALL NOT BE FLEX DUCT. REVISE THE | | DRAWING TO REFLECT THE CODE SECTION BELOW. | | | | 504.8.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A | | SMOOTH INTERIOR FINISH AND SHALL BE CONSTRUCTED OF | | METAL A | | MINIMUM 0.016 INCH (0.4 MM) THICK. THE EXHAUST DUCT | | SIZE SHALL BE 4 INCHES (102 MM) NOMINAL IN DIAMETER. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|